When Action Occurs on Match Time

Setting

SLp1,p2,p3,p4,p5,p6

p1 Box number (01 to 30)
p2 Event type (MATCH_TIME)
p3 Match time number (1 to 3)
p4 Event detection method
EDGE

Edge start

LEVEL

Level start

p5 Action types
p6 Flag numbers (F01 to F60)

Query

SL[p1]?

Example

Set box number 7 to an action in which recording starts

at the time specified for match time 1.
SL07,MATCH_TIME,1,EDGE,MEMORY_START

Explanation The p6 setting is only valid when p5 is FLAG. For the

action types, see section 1.3.

When Action Occurs on USER Key

Setting

SLp1,p2,p3,p4,p5,p6

p1 Box number (01 to 30)
p2 Event type (USER_KEY)
p3 Key number (1, 2)
p4 Event detection method
EDGE

Edge start

LEVEL

Level start

p5 Action types
p6 Flag numbers (F01 to F60)

Query

SL[p1]?

Example

Set box number 8 to an action in which the specified file

is saved upon pressing of USER key 1.
SL08,USER_KEY,1,EDGE,FILE_SAVE

Explanation The p6 setting is only valid when p5 is FLAG. For the

action types, see section 1.3.

SI

Timer Settings

Setting

When p2=OFF

SIp1,p2
When p2=RELATIVE
SIp1,p2,p3,p4
When p2=ABSOLUTE
SIp1,p2,p3,p4

When Not Using the Timer

Setting

SIp1,p2

p1 Timer number (1 to 6)
p2 Timer type (OFF)

Query

SI[p1]?

Example

Set timer number 1 to OFF.

SI1,OFF

When Using the Relative Timer

Setting

SIp1,p2,p3,p4

p1 Timer number (1 to 6)
p2 Timer type (RELATIVE)
p3 Time interval-days (0 to 31)

p4 Time interval-time (HH:MM)
HH hours (00 to 23)
MM

Minute (00 to 59)

(However, when p3 is 0, 00:00 cannot
be set.)

Query

SI[p1]?

Example

Set a relative time of 3 hours and 30 minutes on timer
number 1.
SI1,RELATIVE,0,03:30

When Using the Absolute Timer

Setting

SIp1,p2,p3,p4
p1 Timer number (1 to 6)
p2 Timer type (ABSOLUTE)
p3 Time interval
1M/2M/3M/4M/5M/6M/10M/12M/15M/20M/30M

(minutes)

1H/2H/3H/4H/6H/8H/12H/24H (hours)
p4 Reference time (HH:MM)
HH hours (00 to 23)
MM

Minute (00 to 59)

Query

SI[p1]?

Example

Set a time interval of 30 minutes and a reference time of
17 hours and 15 minutes on timer number 1.
SI1,ABSOLUTE,30M,17:15

SQ

Match Time Settings

Setting

When p2=OFF
SQp1,p2
When p2=MONTH
SQp1,p2,p3,p4
When p2=WEEK
SQp1,p2,p3,p4
When p2=DAY
SQp1,p2,p3

When Not Using the Match Time

Setting

SQp1,p2
p1 Match time number (1 to 3)
p2 Start type (OFF)

Query

SQ[p1]?

Example

Set match timer number 1 to OFF.
SQ1,OFF

When Starting Match Time in Units of Months

Setting

SQp1,p2,p3,p4
p1 Match time number (1 to 3)
p2 Start type (MONTH)
p3 Start date/time-day (1 to 31)
p4 Start date/time-time (HH:MM)
HH hours (00 to 23)
MM

Minute (00 to 59)

Query

SQ[p1]?

Example

Set match time number 1 to 1 day, 8 hours 30 minutes.
SQ1,MONTH,1,08:30

1.4 Setting Commands (System Related)