Ff output of measured/computed fifo data, Fl output of logs, alarm summaries, and status – Yokogawa Standalone MW100 User Manual
Page 49
1-42
IM MW100-17E
1.8 Output Commands
Example
Output the decimal place and units of the channels 1 to
5.
FE1,001,005
Explanation Set a first and last channel number so that the first is
less than or equal to the last.
FF
Output of Measured/Computed
FIFO Data
Setting
When p1=0
FFp1,p2,p3,p4,p5,p6,p7
When p1=1
FFp1,p2
p1 Output type
0
Outputs the FIFO data
1
Outputs the FIFO read range
p2 Measurement groups
1
Data from measurement groups 1
2
Data from measurement groups 2
3
Data from measurement groups 3
p3 First channel (001 to 060 and A001 to
A300)
p4 Last channel (001 to 060 and A001 to
A300)
p5 Read out start position
(-1, 1 to 99999999999)
-1
Latest read position
p6 Read out end position
(-1, 1 to 99999999999)
-1
Latest read position
p7 Max. number of read blocks (1 to
9999)
Example
Output the FIFO read range for measurement group 1.
FF1,1
Explanation • The oldest FIFO buffer data is overwritten with the
newest data in a cyclical manner.
• The output value of p1=1 (output FIFO read range)
is the allowable read range for p1=0 (FIFO data
output).
• Set a first and last channel number so that the first is
less than or equal to the last.
FL
Output of Logs, Alarm
Summaries, and Status
Setting
When p1=0
FLp1,p2,p3
When p1=1
FLp1,p2,p3,p4
When Outputting Logs
Setting
FLp1,p2,p3
p1 Output type (0)
0
Log output
p2 Data type
ERROR
Operation error log
RECORD
Recording log
ALARM
Alarm summary
MESSAGE
Message summary
COM
General purpose
communication log
FTP_C
FTP client log
SMTP
Mail client log
DHCP
DHCP client log
SNTP
Time synchronization
client log
FTP_S
FTP server log
HTTP
HTTP server log
MODBUS_M
Modbus master log
MODBUS_C
Modbus client log
MODBUS_S
Modbus slave log
MODBUS_T
Modbus server log
CIP
CIP server log
PCCC
PCCC slave log
*
MATH
Computation status
*
CMD
Operation log
RECSTATUS Recording status
* Firmware version R3.02 or later
p3 Max. number of read blocks
ERROR
1 to 50
RECORD
1 to 250 (Or "1024" on
models with firmware version R3.02 or
earlier)
ALARM
1 to 256
MESSAGE
1 to 50
COM
1 to 200
FTP_C
1 to 50
SMTP
1 to 50
DHCP
1 to 50
SNTP
1 to 50
FTP_S
1 to 50
HTTP
1 to 50
MODBUS_M
1 to 50
MODBUS_C
1 to 50
MODBUS_S
1 to 50
MODBUS_T
1 to 50
CIP
1 to 50
*
PCCC
1 to 50
*
MATH
1
CMD
1 to 256
RECSTATUS 1
* Firmware version R3.02 or later
Example
Output 10 blocs of the operation error log.
FL0,ERROR,10
Explanation Outputs the log (records) saved to the instrument.
When Outputting Status
Setting
FLp1,p2,p3,p4
p1 Output type (1)
1
Outputs status