IM MW100-17E
1.5 Setting Commands
(Display Related)
ST
Tag Settings
Setting
STp1,p2
p1 Channel range (001 to 060 and A001 to
A300)
p2 Tags (max 15 characters)
Query
ST[p1]?
Example
Set the tag of channel 2 to TAG2.
ST002,TAG2
Explanation • For the characters that can be used for tags, see
user specified characters in section 1.3.
• If the /M1 MATH function option is not included,
MATH channels (A001 to A300) cannot be set
(including queries). However, if the pulse input
module is installed, MATH channels (A001 to A060)
can be set (including queries).
SZ
Zone Settings
Setting
SZp1,p2,p3
p1 Channel range (001 to 060 and A001 to
A300)
p2 Zone lower limit value (0 to 95)[%]
p3 Zone upper limit value (5 to 100)[%]
Query
SZ[p1]?
Example
Zone display channel 2 between 30 and 50%
SZ002,30,50
Explanation • If the /M1 MATH function option is not included,
MATH channels (A001 to A300) cannot be set
(including queries). However, if the pulse input
module is installed, MATH channels (A001 to A060)
can be set (including queries).
• Set total display width of amplitude direction of
waveform display area to 100%.
• A Zone width of less than 5% cannot be set.
• Set the upper and lower zone parameters so that the
upper is greater than the lower.
SC
Display Color Settings
Setting
SCp1,p2
p1 Channel range (001 to 060 and A001 to
A300)
p2 Display color (rrr.ggg.bbb)
rrr RGB R value (0 to 255)
ggg RGB G value (0 to 255)
bbb RGB B value (0 to 255)
Query
SC[p1]?
Example
Set display color of channel 2 to Yellow.
SC002,255.255.0
Explanation If the /M1 MATH function option is not included, MATH
channels (A001 to A300) cannot be set (including
queries). However, if the pulse input module is installed,
MATH channels (A001 to A060) can be set (including
queries).
SB
Display Scale Settings
Setting
SBp1,p2,p3,p4
p1 Channel range (001 to 060 and A001 to
A300)
p2 Scale type
LINEAR Linear display
LOG
Logarithmic display
p3 Number of scale divisions (1 to 12,
AUTO)
p4 Bar graph display reference position
(NORMAL, CENTER)
Query
SB[p1]?
Example
Set the display scale type on channel 2 to LINEAR,
the number of scale divisions to 5, and the reference
position of the bar graph display to NORMAL.
SB002,LINEAR,5,NORMAL
Explanation • If the /M1 MATH function option is not included,
MATH channels (A001 to A300) cannot be set
(including queries). However, if the pulse input
module is installed, MATH channels (A001 to A060)
can be set (including queries).
• If AUTO is specified for p3, the number of divisions is
automatically determined from the upper and lower
limit (If scaling is turned ON in the range settings,
it is determined from the upper and lower limit of
scaling).
• If CENTER is set for p4, the center of the bar graph
is drawn in the reference point.