3 parameters, Channel numbers and channel ranges, Decimal point – Yokogawa Standalone MW100 User Manual
Page 13: Dc voltage
1-6
IM MW100-17E
1.3 Parameters
The numerical value and string parameters of commands have restrictions on format.
The following describes commands whose parameters are restricted.
Channel Numbers and Channel Ranges
Channel Type
Setting Range and Command Setting Parameters
Measurement channels
001-060
Output channels
001-060
Relay
001-060
Channels (type not specified)
001-060
MATH channels
A001-A300
MATH constants
K01-K60
Communication input channels
C001-C300
Flag input channels
F01-F60
Broken-line input channels
P01-P03
• In addition to individual channel numbers, you can specify channel ranges. Use a hyphen
between the first and last channel in the range.
• Channel numbers outside of the range specified above are considered invalid and result in
errors.
• For channels starting with numbers, if you omit the “0” on the front, the channel is still
accepted as long as it lies within the range.
• For channels starting with characters, if you omit a “0” when it is the second or later
character, the channel is still accepted as long as it lies within the range.
Ex.: 1 is recognized as 001, and A1 is recognized as A001.
• If some channels that do not exist are specified in the channel numbers or range, the
specification is considered invalid and an error results. An error also occurs when existing
channels are specified but their corresponding modules are not installed. However, an
error does not occur if all specified channels exist and at least one channel’s corresponding
module is installed (even if one or more channels’ module is not installed).
• Multiple channel ranges cannot be specified at the same time.
• Depending on the installed modules, channels numbers and ranges in setting commands
(display related), control commands, and output commands may not be recognized.
Upper and Lower Limit of Span (Measurement Channels)
Decimal Point
The decimal place is determined for both input and output. The upper and lower limit
values are set without a decimal point, but with the decimal place taken into account.
• DC Voltage
Input Type
Voltage
String
VOLT
Measuring Range
20 mV
60 mV
200 mV
2 V
6 V
20 V
100 V
60 mV (high
resolution)
1 V
6 V (high
resolution)
String
20mV
60mV
200mV
2V
6V
20V
100V
60mVH
1V
6VH
Setting Range for Lower/Upper Limit
of Span
–20.000 to 20.000 mV
–60.00 to 60.00 mV
–200.00 to 200.00 mV
–2.0000 to 2.0000 V
-6.000 to 6.000 V
–20.000 to 20.000 V
–100.00 to 100.00 V
0.000 to 60.000 mV
–1.0000 to 1.0000 V
0.0000 to 6.0000 V
Difference Computation
±20.000 mV
±60.00 mV
±200.00 mV
±2.0000 V
±6.000 V
±20.000 V
±100.00 V
0.000 to 60.000 mV
±1.0000 V
0.0000 to 6.0000 V