App index – Yokogawa Standalone MW100 User Manual
Page 30

1-23
IM MW100-17E
Commands
1
2
3
App
App
Index
When Action Occurs on Digital Input
Setting
SLp1,p2,p3,p4,p5,p6
p1 Box number (01 to 30)
p2 Event type (DI)
p3 Channel numbers (001 to 060)
p4 Event detection method
EDGE
Edge start
LEVEL
Level start
p5 Action types
p6 Flag numbers (F01 to F60)
Query
SL[p1]?
Example
Set box number 02 to computation start action.
SL02,DI,001,EDGE,MATH_START
Explanation • The p6 setting is only valid when p5 is FLAG. For the
action types, see section 1.3.
• Specify a measurement channel number for p3 that
allows contact input.
When Action Occurs on Alarm Output
Setting
SLp1,p2,p3,p4,p5
p1 Box number (01 to 30)
p2 Event type (ALARM)
p3 Event detection method
EDGE
Edge start
LEVEL
Level start
p4 Action types
p5 Flag numbers (F01 to F60)
Query
SL[p1]?
Example
Set box number 3 to recording start action on alarm
occurrence.
SL03,ALARM,LEVEL,MEMORY_START
Explanation The p5 setting is only valid when p4 is FLAG. For the
action types, see section 1.3.
When Action Occurs on Recording Start
Setting
SLp1,p2,p3,p4,p5
p1 Box number (01 to 30)
p2 Event type (MEMORY)
p3 Event detection method
EDGE
Edge start
LEVEL
Level start
p4 Action types
p5 Flag numbers (F01 to F60)
Query
SL[p1]?
Example
Set box number 4 to the alarm acknowledge action.
SL04,MEMORY,EDGE,ALARM_ACK
Explanation The p5 setting is only valid when p4 is FLAG. For the
action types, see section 1.3.
When Action Occurs on Occurrence of Alarm on
Certain Channel
Setting
SLp1,p2,p3,p4,p5,p6.p7
p1 Box number (01 to 30)
p2 Event type (ALARM_CH)
p3 Channel numbers (001 to 060 and A001
to A300)
p4 Alarm number (1 to 4)
p5 Event detection method
EDGE
Edge start
LEVEL
Level start
p6 Action types
p7 Flag numbers (F01 to F60)
Query
SL[p1]?
Example
Set box number 5 to recording start/stop action on
occurrence of alarm on channel 1.
SL05,ALARM_CH,001,1,LEVEL,MEMORY_START
Explanation • The p7 setting is only valid when p6 is FLAG. For
the action types, see section 1.3.
• Specify measurement channels on 001 to 060 of p3.
• If the /M1 MATH function option is not included,
MATH channels (A001 to A300) cannot be set
(including queries). However, if the pulse input
module is installed, MATH channels (A001 to A060)
can be set (including queries).
When Action Occurs on Relay Operation
Setting
SLp1,p2,p3,p4,p5,p6
p1 Box number (01 to 30)
p2 Event type (RELAY)
p3 Relay numbers (001 to 060)
p4 Event detection method
EDGE
Edge start
LEVEL
Level start
p5 Action types
p6 Flag numbers (F01 to F60)
Query
SL[p1]?
Example
Set box number 5 to an action of activation of trigger 1
upon change in status of relay 1.
SL06,RELAY,001,EDGE,TRIGGER1
Explanation • The p6 setting is only valid when p5 is FLAG. For
the action types, see section 1.3.
• Specify relay number on p3.
When Action Occurs on Timer
Setting
SLp1,p2,p3,p4,p5,p6
p1 Box number (01 to 30)
p2 Event type (TIMER)
p3 Timer number (1 to 6)
p4 Event detection method
EDGE
Edge start
LEVEL
Level start
p5 Action types
p6 Flag numbers (F01 to F60)
Query
SL[p1]?
Example
Set box number 6 to an action in which computation
starts every time specified for timer 1.
SL06,TIMER,1,EDGE,MATH_START
Explanation The p6 setting is only valid when p5 is FLAG. For the
action types, see section 1.3.
1.4 Setting Commands (System Related)