Ml recording data length settings, Mr recording free space settings, Mx thinning recording operation settings – Yokogawa Standalone MW100 User Manual
Page 35: Mu setting save operation settings, Xk key lock settings
1-28
IM MW100-17E
Explanation • Set p5 (recording interval) to an integer multiple of the
measurement interval.
The recording interval can be set to 1, 2, 4, or 10 if
the measurement interval is 50 mS, 500 mS, or 5 S.
The recording interval can be set to 1, 5, or 10 if the
measurement interval is 200 mS.
The recording interval can be set to 1, 2, 5, or 10 for
all other measurement intervals.
ML
Recording Data Length Settings
Setting
MLp1
p1 Data length when the recording
start timing is set to DIRECT under
recording operation
30 M (units of minutes)
1H/2H/3H/4H/6H/8H/12H (units of
hours)
1D/2D/3D/5D/7D/10D/14D/31D (units of
days)
Query
ML?
Example
Set the recording start time data length to 1 hour.
ML1H
MR
Recording Free Space Settings
Setting
MRp1
p1 Recording time remaining on media set
for small media free space
1H/2H/3H/4H/5H (units of hours)
Query
MR?
Example
Set media free space to 2 hours.
MR2H
MX
Thinning Recording Operation
Settings
Setting
When p1=OFF
MXp1
When p1 is not OFF
MXp1,p2,p3
p1 Recording interval:
OFF (do not record)
4S/5S/10S/20S/30S (units of seconds)
1M/2M/3M/4M/5M/10M/20M/30M (units of
minutes)
1H (units of hours)
p2 Recording stop action
SINGLE Recording stops after
creating one file
FULLSTOP Recording stops when file is
full
ROTATE Continue recording by
deleting the old data
p3 Recording data length
30 M (units of minutes)
1H/2H/3H/4H/6H/8H/12H (units of
hours)
1D/2D/3D/5D/7D/10D/14D/31D (units of
days)
Query
MX?
Example
Set recording interval to 1H, recording operation to
FULLSTOP, and recording data length to 2D.
MX1H,FULLSTOP,2D
Explanation • p3 cannot be set to a time less than the p1 interval.
• The relationship between the measurement and
MATH intervals set on the input module and the
allowed thinning recording interval setting is shown
in the table below.
4S
5S
10S
20S
30S
1M
2M
3M
4M
5M
10M
20M
30M
1H
10ms, 50ms, 100ms
200ms, 500ms, 1s
2s
10s
Measurement Interval (Measurement Group/MATH Interval)
5s
20s
30s
60s
: Can be set, Blank: Cannot be set
Thinning
Recording
Interval
MU
Setting Save Operation Settings
Setting
MUp1,p2,p3,p4
p1 Saving of channel related settings
OFF/ON
p2 Saving of recording related settings
OFF/ON
p3 Saving of communication related
settings OFF/ON
p4 Saving of other settings OFF/ON
Query
MU?
Example
Set so that all settings are saved.
MHON,ON,ON,ON
XK
Key Lock Settings
Setting
XKp1
p1 Key lock OFF/ON
Query
XK?
Example
Key lock settings.
XKON
Explanation The setting is valid in Setting mode or Measurement
mode.
1.4 Setting Commands (System Related)