App index, Sf filter settings, Xb burnout settings – Yokogawa Standalone MW100 User Manual

Page 24: Xj reference junction compensation settings, Pf pulse input module chattering filter settings

background image

1-17

IM MW100-17E

Commands

1

2

3

App

App

Index

When Setting Scaling

Setting

SRp1,p2,p3,p4,p5,p6,p7,p8,p9,p10

p1 Channel range (001 to 060)
p2 Input type
VOLT

DC voltage

TC

Thermocouple

RTD

Resistance temperature
detector

DI

Contact input

OHM

Resistance input

STR

Strain input

PULSE

Pulse

p3 Measuring range
p4 Lower limit of span
p5 Upper limit of span
p6 MATH type (SCALE)
p7 Scaling lower limit (-30000 to 30000)
p8 Scaling upper limit (-30000 to 30000)
p9 Decimal place (0 to 4)
p10 Unit (max 6 characters)

Query

SR[p1]?

Example

Convert the DC voltage measured on channel 2 to
DC current. Set the measuring range to 6V (high
resolution), lower limit of span to 1 V, upper limit of span
to 5 V, lower limit of scaling to 0.00A, and upper limit of
scaling to 5.00A.
SR002,VOLT,6VH,10000,50000,SCALE,0,500,
2,A

Explanation • Set the p3, p4, and p5 setting parameters according

to the table in section 1.3.

• Specify measurement channels on p1.
• For the characters that can be used for p10, see

user specified characters in section 1.3.

SF

Filter Settings

Setting

SFp1,p2
p1 Channel range (001 to 060)
p2 Filter coefficient (0, 5, 10, 20, 25,

40, 50, 100)

Query

SF[p1]?

Example

Set the filter coefficient for channel 2 to 5.
SF002,5

Explanation Specify measurement channels on p1. However, do not

set this on the channels of the digital input module.

XB

Burnout Settings

Setting

XBp1,p2
p1 Channel range (001 to 060)
p2 Burnout processing (OFF, UP, DOWN)

Query

XB[p1]?

Example

Set UP (+OVER) when burnout occurs on channel 1.
XB001,UP

Explanation Specify measurement channels that can accept TC

input for p1.

XJ

Reference Junction

Compensation Settings

Setting

When p2=INT

XJp1,p2

When p2=EXT

XJp1,p2,p3

For an Internal Compensation Circuit

Setting

XJp1,p2
p1 Channel range (001 to 060)
p2 Reference junction compensation

selection (INT)

Query

XJ[p1]?

Example

Set RJC on channel 1 to internal
compensation circuit.
XJ001,INT

Explanation Specify measurement channels that can accept TC

input for p1

For External RJC

Setting

XJp1,p2,p3
p1 Channel range (001 to 060)
p2 Reference junction compensation

selection (EXT)

p3 External RJC value (-20000 to 20000)

Query

XJ[p1]?

Example

Set RJC on channel 2 to external RJC, and the
compensation value to 0 µV.
XJ002,EXT,0

Explanation • Units of p3 are µV.

• Specify measurement channels that can accept TC

input for p1.

PF

Pulse Input Module Chattering

Filter Settings

Setting

PFp1,p2

p1 Channel range (001 to 060)

p2 Chattering filtering (OFF/ON)

Query

PF[p1]?

Example

Turn on the chattering filter on channel 23.

PF23,ON

Explanation For p1, specify channels included on the pulse input

module.

1.4 Setting Commands (System Related)