IM MW100-17E

YU

Mail Contents Settings

Setting

When p1=TIME
YUp1,p2,p3,p4,p5
When p1=ALARM
YUp1,p2,p3
When p1 is neither TIME, ALARM, nor REPORT
YUp1,p2

For other than report notification

Setting

YUp1,p2,p3,p4,p5
p1 Send contents
ALARM Alarm notification
FILE

File creation notification

MEDIA

Media free space

notification

POWER

Startup notification

SYSTEM Setting error notification
TIME

Periodic report

p2 Recipient
OFF

Do not send

1

Send to recipient address 1

2

Send to recipient address 2

1_2

Send to recipient addresses

1 and 2

p3 Add instantaneous value data ON/OFF
p4 Send interval (1/2/3/4/6/8/12/24)[hours]
p5 Reference time (HH:MM)
HH

hours (00 to 23)

MM

Minute (00 to 59)

Query

YU?

Example

Set mail to recipients 1 and 2 daily at 18:00 with an
instantaneous value data attachment.
YUTIME,1_2,ON,24,18:00

For report notification

Setting

YUp1,p2,p3,p4,p5,p6,p7,p8,p9,p10,p11

p1 Sent contents
REPORT Notification of report

results

p2 Recipient
OFF

Do not send

1

Send to recipient address 1

2

Send to recipient address 2

1_2

Send to recipient addresses
1 and 2

p3 Send when creating hourly report

(OFF/ON)

p4 Send when creating daily report

(OFF/ON)

p5 Send when creating weekly report

(OFF/ON)

p6 Send when creating monthly report

(OFF/ON)

p7 Add maximum value data (OFF/ON)
p8 Add minimum value data (OFF/ON)
p9 Add average value data (OFF/ON)
p10 Add integral value data (OFF/ON)
p11 Add instantaneous value data (OFF/ON)

Query

YU?

Example

Add maximum and integral values when daily report is
created and send to recipient 1
YUREPORT,1,OFF,ON,OFF,OFF,ON,OFF,OFF,ON,
OFF

Explanation You cannot enter REPORT settings on products without

the /M3 report function option.

YC

E-Mail Alarm Transmission

Settings

Setting

YCp1
p1 Channel structure (up to 100

characters)

Query

YC?

Example

Set the channels for mail alarm transmission judgement
to A001 to A005.
YCA001-A005

Explanation • See section 1.3 for the channel structure.

• You can specify measurement and MATH channels

(only with the /M1 MATH function option and when
the pulse input module is installed).

YT

Time Synchronization Settings

Setting

YTp1,p2,p3,p4
p1 SNTP server name (up to 64

characters)

p2 Port number (1 to 65535)
p3 Reference time (HH:MM)
HH

hours (00 to 23)

MM

Minute (00 to 59)

p4 Query interval (3H/12H/24H) [hours]

Query

YT?

Example

Set time synchronization for once daily at 5:00.
YTsntp_server.abc.com,123,05:00,24H

1.6 Setting Commands (Communication Related)