Yu mail contents settings, Yc e-mail alarm transmission settings, Yt time synchronization settings – Yokogawa Standalone MW100 User Manual
Page 41
1-34
IM MW100-17E
YU
Mail Contents Settings
Setting
When p1=TIME
YUp1,p2,p3,p4,p5
When p1=ALARM
YUp1,p2,p3
When p1 is neither TIME, ALARM, nor REPORT
YUp1,p2
For other than report notification
Setting
YUp1,p2,p3,p4,p5
p1 Send contents
ALARM Alarm notification
FILE
File creation notification
MEDIA
Media free space
notification
POWER
Startup notification
SYSTEM Setting error notification
TIME
Periodic report
p2 Recipient
OFF
Do not send
1
Send to recipient address 1
2
Send to recipient address 2
1_2
Send to recipient addresses
1 and 2
p3 Add instantaneous value data ON/OFF
p4 Send interval (1/2/3/4/6/8/12/24)[hours]
p5 Reference time (HH:MM)
HH
hours (00 to 23)
MM
Minute (00 to 59)
Query
YU?
Example
Set mail to recipients 1 and 2 daily at 18:00 with an
instantaneous value data attachment.
YUTIME,1_2,ON,24,18:00
For report notification
Setting
YUp1,p2,p3,p4,p5,p6,p7,p8,p9,p10,p11
p1 Sent contents
REPORT Notification of report
results
p2 Recipient
OFF
Do not send
1
Send to recipient address 1
2
Send to recipient address 2
1_2
Send to recipient addresses
1 and 2
p3 Send when creating hourly report
(OFF/ON)
p4 Send when creating daily report
(OFF/ON)
p5 Send when creating weekly report
(OFF/ON)
p6 Send when creating monthly report
(OFF/ON)
p7 Add maximum value data (OFF/ON)
p8 Add minimum value data (OFF/ON)
p9 Add average value data (OFF/ON)
p10 Add integral value data (OFF/ON)
p11 Add instantaneous value data (OFF/ON)
Query
YU?
Example
Add maximum and integral values when daily report is
created and send to recipient 1
YUREPORT,1,OFF,ON,OFF,OFF,ON,OFF,OFF,ON,
OFF
Explanation You cannot enter REPORT settings on products without
the /M3 report function option.
YC
E-Mail Alarm Transmission
Settings
Setting
YCp1
p1 Channel structure (up to 100
characters)
Query
YC?
Example
Set the channels for mail alarm transmission judgement
to A001 to A005.
YCA001-A005
Explanation • See section 1.3 for the channel structure.
• You can specify measurement and MATH channels
(only with the /M1 MATH function option and when
the pulse input module is installed).
YT
Time Synchronization Settings
Setting
YTp1,p2,p3,p4
p1 SNTP server name (up to 64
characters)
p2 Port number (1 to 65535)
p3 Reference time (HH:MM)
HH
hours (00 to 23)
MM
Minute (00 to 59)
p4 Query interval (3H/12H/24H) [hours]
Query
YT?
Example
Set time synchronization for once daily at 5:00.
YTsntp_server.abc.com,123,05:00,24H
1.6 Setting Commands (Communication Related)