Ap preset operation settings, Sl event action settings – Yokogawa Standalone MW100 User Manual
Page 29
1-22
IM MW100-17E
Query
AO[p1]?
Example
Set transmission output on channel 11 to 4-20 mA
relative to the measured values on channel 1.
AO011,AO,TRANS,20mA,4000,20000,0,001
Explanation • Specify output channels on p1.
• When entering the setting parameters of p5, p6, and
p7, exclude the decimal point.
• If the /M1 MATH function option is not included,
MATH channels (A001 to A300) cannot be set
(including queries) on p8. However, if the pulse input
module is installed, MATH channels (A001 to A060)
can be set (including queries).
When Setting PWM Channels
Setting
When using arbitrary output
AOp1,p2,p3,p4,p5,p6,p7,p8
When using transmission output
AOp1,p2,p3,p4,p5,p6,p7,p8,p9
p1 Channel range (001 to 060)
p2 Output type (PWM)
p3 Output method
TRANS
Transmission output
COM
arbitrary output
p4 Output range
1 mS
1 ms interval output
10 mS
10 ms interval output
p5 Lower limit of span (0.001% units,
0 to 100000)
p6 Upper limit of span (0.001% units,
0 to 100000)
p7 Pulse interval (specify as a
multiple)
1 to 30000 (both p4:1mS and 10mS same
range)
p8 Preset value (0.001% units,
0 to 100000)
p9 Reference channel
001 to 060 or A001 to A300
Query
AO[p1]?
Example
Set output on channel 12 to arbitrary output.
AO012,PWM,COM,1mS,0,100000,10,100000
Explanation • Specify output channels on p1.
• Channels set to SKIP are not output.
• If the /M1 MATH function option is not included,
MATH channels (A001 to A300) cannot be set
(including queries) on p9. However, if the pulse input
module is installed, MATH channels (A001 to A060)
can be set (including queries).
• When p4=10ms, p7=10, the pulse interval is 10 x 10
= 100 ms.
AP
Preset Operation Settings
Setting
APp1,p2,p3,p4
p1 Channel range (001 to 060)
p2 Operation upon startup
LAST
Hold previous value
PRESET Output preset value
p3 Operation upon errors
LAST
Hold previous value
PRESET Output preset value
p4 Operation upon measurement stop,
computation stop, or transmission
stop (Firmware version R3.03 or
later)
LAST
Hold previous value
PRESET Output preset value
Query
AP[p1]?
Example
Set the operation upon startup for channel 1 to
PRESET, and operation upon errors to LAST.
AP001,PRESET,LAST
Explanation Specify output channels on p1.
SL
Event Action Settings
Setting
When p2=OFF
SLp1,p2
When p2=DI
SLp1,p2,p3,p4,p5,p6
When p2=ALARM
SLp1,p2,p3,p4,p5
When p2=MEMORY
SLp1,p2,p3,p4,p5
When p2=ALARM_CH
SLp1,p2,p3,p4,p5,p6,p7
When p2=RELAY
SLp1,p2,p3,p4,p5,p6
When p2=TIMER
SLp1,p2,p3,p4,p5,p6
When p2=MATCH_TIME
SLp1,p2,p3,p4,p5,p6
When p2=USER_KEY
SLp1,p2,p3,p4,p5,p6
When Action Does Not Occur
Setting
SLp1,p2
p1 Box number (01 to 30)
p2 Event type (OFF)
Query
SL[p1]?
Example
Set box number 01 to no action.
SL01,OFF
1.4 Setting Commands (System Related)