beautypg.com

Upper and lower limit of span (math channels), Upper and lower limit of scaling, Alarm types – Yokogawa Standalone MW100 User Manual

Page 16: Alarm value setting range, Hysteresis value setting range, App index

background image

1-9

IM MW100-17E

Commands

1

2

3

App

App

Index

• PWM Output

Ouput Type

PMW

String

PMW

Output Range

PMW output (1ms)

PMW output (10ms)

String

1mS

10mS

Pulse Interval Range*

1 to 30000 ms

10 to 300000 ms

Span Setting

Range

0.000 to 100.000%

* Settings of 1 to 30000 ms (1 ms range) and 10 to 30000 ms (10 ms range) are allowed, but the setting

command is specified as a multiple of the output range. Refer to the AO command in section 1.4.

Note

For information on the measurement accuracy at each measuring range, see the MW100 Data
Acquisition Unit User’s Manual
(IM MW100-01E).

Upper and Lower Limit of Span (MATH Channels)

Set the mantissa between –9999999 and 99999999. Set the decimal place in the range
from 0 to 4.

Upper and Lower Limit of Scaling

Set between –30000 and 30000. Set the decimal place in the range from 0 to 4.

Alarm Types

The following shows alarm types that can be set by channel and input type.

Channel Type Input Type

MATH Type Alarm Type

Hi/Lo lim

(H/L)

Diff. H/L

lim (DH/

DL)

RoC lim.

on inc/dec

(RH/RL)

Delay on

inc/dec

(TH/TL)

Meas channels SKIP

-

No

No

No

No

VOLT/TC/

RTD/DI/OHM/

STR/PULSE

OFF

Yes

No

Yes

Yes

Scale

Yes

No

Yes

Yes

Diff. comp

Yes

Yes

Yes

Yes

RRJC

-

Yes

No

Yes

Yes

MATH channels -

OFF

No

No

No

No

ON

Yes

No

No

Yes

Yes: Can be set, No: Cannot be set

Alarm Value Setting Range

The following shows the setting ranges for alarm values.

Measurement Channels

Alarm Type

Computation Type

Alarm Value Setting Range

H/L

OFF/DELTA/RRJC

Normal mode span setting range

SCALE

Scale Low to High limit (low limit < high limit)

Scale High to Low limit (high limit < low limit)

DH/DL

DELTA

Difference mode span setting range

RH/RL

OFF/DELTA/RRJC

1 to width of normal mode span setting range

SCALE

1 to width of scale upper/lower limit values

TH/TL

OFF/DELTA/RRJC

Normal mode span setting range

SCALE

Scale Low to High limit (low limit < high limit)

Scale High to Low limit (high limit < low limit)

MATH Channels

Within the MATH channels span range (–9999999 to 9999999 (mantissa))

Hysteresis Value Setting Range

The following shows the setting ranges for hysteresis values. The set hysteresis does not
apply to the upper/lower limit on rate-of-change alarm.

Alarm Type

Hysteresis Value Setting Range

H/DH/TH

0 to (alarm value – alarm value setting range lower limit)

L/DL/TL

0 to (alarm value setting range upper limit – alarm value)

1.3 Parameters