Display Possible Problem
Corrective Action
E111
Invalid channel number for alarm event.
Set an input module or MATH channel number.
E112
Invalid relay number for relay event.
Set the channel number for the DO module.
E113
Invalid action type.
Enter a correct action type.
E114
Invalid combination of edge and level detection Set the edge and legel detection types to something different.
actions.
E115
Invalid combination of level detection actions.
Set events of different types to different actions in level detection.
E116
Invalid flag number.
Enter a correct flag number.
E120 Invalid measurement group number.
Set the measurement interval so that meas. gr 1 ≤ meas. gr 2
≤ meas. gr 3. The maximum allowable ch for 10 ms measurement
is 10, and for 50 ms, 30.
E121 Invalid measurement group number for MATH
Set MATH interval to a measurement group of 100 ms or longer.
interval.
E130 Size of data file for measurement group 1
Set the number of saved channels, recording interval, and
exceeds the upper limit.
recording data length so that the data file of measurement group 1
does not exceed 10 MB.
E131 Size of data file for measurement group 2
Set the number of saved channels, recording interval, and
exceeds the upper limit.
recording data length so that the data file of measurement group 2
does not exceed 10 MB.
E132 Size of data file for measurement group 3
Set the number of saved channels, recording interval, and
exceeds the upper limit.
recording data length so that the data file of measurement group 3
does not exceed 10 MB.
E133 Size of MATH data file exceeds the upper limit.
Set the number of saved channels, recording interval, and
recording data length so that the MATH data file does not exceed
10 MB.
E134 Size of thinned data file exceeds the upper limit. Set the number of saved channels, recording interval, and
recording data length so that the thinned data file does not exceed
10 MB.
E135 Cannot set smaller value for thinning recording
Set a value for the thinning recording interval higher than the
interval than measuring or MATH interval.
measurement and MATH interval.
E136 Invalid combination of thinning recording,
Set a value for the thinning recording interval that is a common
measuring and MATH interval.
multiple of the measurement and MATH intervals.
E137 The combination of the thinning recording interval Set the thinning recording data length to an integer multiple of the
and the thinning recording data length is not
thinning recording interval.
correct.
E138 Cannot set recording operation for measurement Set the measurement interval of the measurement group number to
group with no measuring interval.
something other than OFF.
E139 Invalid recording interval.
Set a recording interval allowed for the measurement interval of the
measurement group.
E140 Upper and lower limits of the display zone cannot Set the upper and lower limits of display zone to a different value.
be equal.
E141 Cannot set smaller value than lower limit of
Set a larger value for the upper limit than that of the lower limit.
display zone for upper limit.
E142 Width of display zone must be 5% of that of the Set the upper and lower limits so that the difference between them
entire display or more.
is 5% or more.
E145 Incorrect display group format.
Enter a display group of the correct format.
E150 IP address must belong to class A, B, or C.
Set an IP address belonging to class A, B, or C.
E151 Net or host part of IP address is all 0’s or 1’s.
Set a valid combination of IP address and subnet mask.
E152 Invalid subnet mask.
Enter a setting according to your network.
E153 Invalid gateway address.
Make sure that the network part of the IP address and default
gateway match.
E160 Incorrect alarm e-mail channel format.
Specify a channel using the correct format.
E165 Invalid channel number for Modbus command.
Enter a correct channel.
E166 Invalid combination of start and end channel for Set a first and last channel of the same type.
Modbus command.
E167 Invalid sequence of start and end channel for
Set the last channel equal or greater than the first channel.
Modbus command.
E168 Too many channels for command number.
Set a valid number of channels for the data type.
E170 Invalid channel number for report.
Set the channel included on the input module.
Appendix 7 Error Display on the 7-Segment LED and Corrective Actions