Output of system recognition status (cf), Output of system recognition status (cf) -38, Syntax – Yokogawa Standalone MW100 User Manual
Page 88: Example
2-38
IM MW100-17E
2.2 ASCII Output
Output of System Recognition Status (CF)
• Output using the CF command.
• Regardless of the base unit type, 6 slots of module information is always output.
Syntax
EACRLF
n_S=aaa-bbb-ccc_R=aaa-bbb-ccc_mmm...mCRLF
n_S=aaa-bbb-ccc_R=aaa-bbb-ccc_mmm...mCRLF
n_S=aaa-bbb-ccc_R=aaa-bbb-ccc_mmm...mCRLF
n_S=aaa-bbb-ccc_R=aaa-bbb-ccc_mmm...mCRLF
n_S=aaa-bbb-ccc_R=aaa-bbb-ccc_mmm...mCRLF
n_S=aaa-bbb-ccc_R=aaa-bbb-ccc_mmm...mCRLF
ENCRLF
n
Module number (0 to 5)
S=
Status of modules set on the system
R=
Status of modules actually installed
aaa:
Module model
bbb:
Module basic specifications code (input/output type)
ccc:
Module basic specifications code (measuring interval, no. of channels)
mmm...m Module error status (10 characters)
RomError:
EEPROM damaged
CalError:
Calibration value damaged
SlotError:
30-CH Medium Speed DCV/TC/DI Input Module installed in
invalid slot.
_
Blank: Normalize without error
Example
EA
0 S=MX110-UNV-H04 R=MX110-UNV-H04
1 S=MX110-UNV-M10 R=MX110-UNV-M10 CalError
2 S=MX110-UNV-M10 R=MX110-UNV-H04
3 S=MX115-D05-H10 R=MX115-D05-H10
4 S=MX125-MKC-M10 R=-------------
5 S=------------- R=-------------
EN