Output of alarm summaries (fl0, alarm), Output of alarm summaries (fl0, alarm) -14 – Yokogawa Standalone MW100 User Manual
Page 64
2-14
IM MW100-17E
Output of Alarm Summaries (FL0, ALARM)
• Output using the FL command.
• Alarm summaries are output. Up to 256 past alarms are retained. If that number is
exceeded, old alarms are overwritten with new ones.
Syntax
EACRLF
yy/mo/dd_hh:mm:ss.ttt_cccc_ls_aaa..CRLF
...................................................
ENCRLF
yy
Yea
r (00 to
99)
mo
Month (01 to 12)
dd
Day (01 to 31)
hh
Hour (00 to 23)
mm
Minute (00 to 59)
ss
Seconds (00 to 59)
ttt
Miliseconds (000 to 999)
cccc
Channel numbers (001 to 060 or A001 to A300)
l
Alarm level (1 to 4)
s
Alarm type (
H
,
h
,
L
,
l
,
R
,
r
,
T
,
t
)
H
:
Upper limit alarm
h
:
Differential upper limit alarm
L
:
Lower limit alarm
l
:
Differential lower limit alarm
R
:
Upper limit on rate-of-change alarm
r
:
Lower limit on rate-of-change alarm
T
:
Delay upper limit alarm
t
:
Delay lower limit alarm
aaa..
Alarm status (off,on)
off
:
Alarm clear
on
:
alarm occurs
_
Blank
(Note)
When acknowledging alarm, AlarmAck is output in a position on and after the
cccc channel number.
Example
EA
05/04/01 12:20:00.000 001 1L on
05/04/01 12:20:00.000 A001 3t off
05/04/01 13:00:00.000 AlarmAck
EN
2.2 ASCII Output