Page 108

background image

App-6

IM MW100-17E

Note

• For INT32 or INT16, only the mantissa of the measured/computed data is acquired. The

decimal place must be obtained separately.

• For FLOAT, the measured/computed data including the decimal place can be acquired.
• The FLOAT and INT32 data domains are set so that they can only be accessed (read/write)

by the unit of two registers.

• Alarm statuses are output in the same format as those described in section 2.3, “Binary

Output.”

Hold Registers

41001 to 41600, and 42001 to 42300 are for functions of firmware version R3.04 or later.

Absolute

Relative Allocation

Data

Address

Address

Type

40001

0000

Lower byte of data from communication input channel C001 FLOAT

40002

0001

Upper byte of data from communication input channel C001

:

:

:

:

40599

0598

Lower byte of data from communication input channel C300 FLOAT

40600

0599

Upper byte of data from communication input channel C300

41001

1000

Lower byte of data from communication input channel C001 INT32

41002

1001

Upper byte of data from communication input channel C001

:

:

:

:

41599

1598

Lower byte of data from communication input channel C300 INT32

41600

1599

Upper byte of data from communication input channel C300

42001

2000

Data from communication input channel C001

INT16

:

:

:

:

42300

2299

Data from communication input channel C300

INT16

Appendix 2 Modbus Protocol