beautypg.com

App index, Bd delay alarm settings, Xd relay settings – Yokogawa Standalone MW100 User Manual

Page 26: So expression settings

background image

1-19

IM MW100-17E

Commands

1

2

3

App

App

Index

BD

Delay Alarm Settings

Setting

BDp1,p2
p1 Channel number (001 to 060 or A001 to

A300)

p2 Alarm delay (1 to 3600 s)

Query

BD[p1]?

Example

Set the alarm delay of channel 1 to 20 s.
BD001,20

Explanation Set the delay time to an integer multiple of the

measurement or MATH interval.

XD

Relay Settings

Setting

When p2=MEDIA, FAIL, or ERROR
XDp1,p2
When p2=COM
XDp1,p2,p3
When p2=ALARM, p4=ON, or p5=AND
XDp1,p2,p3,p4,p5
When p2=ALARM, p4=OFF, or p5=OR
XDp1,p2,p3,p4,p5,p6,p7,p8
p1 Relay range (001 to 060)
p2 Relay output type
ALARM Alarm
COM

Communication input

MEDIA

Media free space

FAIL

FAIL output

ERROR

Error output

p3 Relay energized/de-energized
ENERG

Energize

DE_EN

De-energize

p4 Relay status hold (OFF/ON)
p5 Relay operation conditions
AND

Operate when all specified
alarms are on alarm status.

OR

Operate when at least one
of the specified alarms is
alarm status.

p6 Reflash function (OFF/ON)
p7 Preset value upon error (Firmware

version R3.03 or later)

OFF
OPEN Opens (de-energizes) the output

relay upon stop

CLOSE Closes (energizes) the output

relay upon stop

p8 Preset value upon stop (Firmware

version R3.03 or later)

OFF
OPEN Opens (de-energizes) the output

relay upon stop

CLOSE Closes (energizes) the output

relay upon stop

Query

XD[p1]?

Example

Set relay number 11 to energize, relay status hold to OFF,
relay operation condition to OR, and reflash function to ON.
XD11,ALARM,ENERG,OFF,OR,ON

1.4 Setting Commands (System Related)

Explanation • Specify relay on p1.

• If the relay on p1 is set to the relay number of the

SA command, if you change the output type the SA
command’s relay number turns OFF.

• The relay output type and affirmative/negative of the

parameter settings are shown below.

Relay Output

Type

Energize/

De-energize

Hold/

Non-Hold

No (fixed to

non-hold)

No (fixed to

non-hold)

No (fixed to

non-hold)
No (fixed to

non-hold)

Yes

Yes

Yes

Yes

Yes

No

(fixed to

energize)

No

(fixed to

energize)

No

(fixed to

de-energize)

ALARM

COM

MEDIA

FAIL

ERROR

AND/OR

Reflash

Function

No (fixed to

OR)

No (fixed to

OFF)

No (fixed to

OFF)

No (fixed to

OFF)
No (fixed to

OFF)

No (fixed to

OR)

No (fixed to

OR)
No (fixed to

OR)

• The reflash alarm can only be used when the relay

status is non-hold (OFF) and the relay operation
condition is OR.

• The preset value (OPEN/CLOSE) is only valid when

the DO type is alarm DO, and the condition is: “relay
operation is non-hold” OR “reflash is OFF.”

• When the preset value (OPEN/CLOSE) occurs,

priority is given over the alarm relay output, and the
preset output is carried out.

SO

Expression Settings

Setting

When p2=OFF
SOp1,p2
When p2=ON
SO p1,p2,p3,p4,p5,p6,p7
p1 MATH channel range (A001 to A300)
p2 MATH ON/OFF
p3 Expression (A001 to A060: max. 120

characters, A061 to A300: max. 10
characters

*

)

* Or "8 characters" on models with

firmware version R3.02 or earlier

p4 Lower limit of span (-9999999 to

99999999)

p5 Upper limit of span (-9999999 to

99999999)

p6 Span decimal place (0 to 4)
p7 Units (max 6 characters)

Query

SO[p1]?

Example

Turn MATH on MATH channel number 31 ON, set the
expression to the sum of channels 1 and 2, set lower
limit of span to 1.0000, upper limit of span to 5.0000,
and units to V.
SOA031,ON,001+002,10000,50000,4,V

Explanation • You can set this command on products with the

/M1 MATH function option, or when the pulse input
module is installed. The MATH channel range when
the pulse input module is installed is (A001 to A060).

• For expressions, see the MW100 Data Acquisition

Unit User’s Manual (IM MW100-01E).