App index, Vl broken-line input channel settings, Ao output range settings – Yokogawa Standalone MW100 User Manual
Page 28
1-21
IM MW100-17E
Commands
1
2
3
App
App
Index
SEC The integral value of data
from each measurement or MATH
interval ÷ computations per
second
MIN The integral value of data
from each measurement or MATH
interval ÷ computations per
minute
HOUR The integral value of data
from each measurement or MATH
interval ÷ computations per hour
DAY The integral value of data
from each measurement or MATH
interval ÷ computations per day
p5 Displayed unit string for integration
(max 6 characters)
Query
RM[p1]?
Example
Turn ON box number 1, set the channel to 002, set the
integration unit of time to hourly, and the unit string to
kg/h.
RM01,ON,HOUR,kg/h
Explanation • You can set this command on products with the /M3
report function option.
• If the /M1 MATH function option is not included,
MATH channels (A001 to A300) cannot be set
(including queries). However, if the pulse input
module is installed, MATH channels (A001 to A060)
can be set (including queries).
• For the characters that can be used for p5, see
“User Specified Strings” in section 1.3.
VL
Broken-Line Input Channel
Settings
Setting
When not using broken line
VLp1,p2
When using broken line
VLp1,p2,p3,p4,....p33,p34
p1 Sets broken-line input channels (P01
to P03)
p2 Use/do not use broken line
OFF
Do not use
SINGLE Execute 1 cycle
REPEAT Execute repeatedly
p3-p34 Point structure (point notation
(xx.yy))
xx
Break point time (0 to 86400
(sec.))
yy
Break point output value
(-30000 to 30000)
Query
VL[p1]?
Example
Set broken line input channel p1 to a point structure of
0:100, 60:200, 120:200, 180:100.
VLP01,SINGLE,(0.100),(60.200),(120.200),
(180.100),(-1.0)
Explanation • You can set this command on products with the /M1
MATH function option.
• The p3 of break point time is fixed at 0 seconds.
• Set the break point time in ascending order. You
cannot set multiple output values to the same time.
• You must set the end of the point structure to (–1.0).
• When broken line usage is SINGLE or REPEAT, and
there is not even 1 point set for the point structure,
this cannot be set.
AO
Output Range Settings
Setting
When p2=SKIP
AOp1,p2
When p2=AO
When p3=COM
AOp1,p2,p3,p4,p5,p6,p7
When p3=TRANS
AOp1,p2,p3,p4,p5,p6,p7,p8
When p2=PWM
When p3=COM
AOp1,p2,p3,p4,p5,p6,p7,p8
When p3=TRANS
AOp1,p2,p3,p4,p5,p6,p7,p8,p9
When Setting SKIP
Setting
AOp1,p2
p1 Channel range (001 to 060)
p2 Output type (SKIP)
Query
AO[p1]?
Example
Skip channel 1.
AO001,SKIP
Explanation Specify output channels on p1.
When Setting AO Channels
Setting
When using arbitrary output
AOp1,p2,p3,p4,p5,p6.p7
When using transmission output
AOp1,p2,p3,p4,p5,p6,p7,p8
p1 Channel range (001 to 060)
p2 Output type (AO)
p3 Output method
TRANS
Transmission output
COM
Arbitrary output
p4 Output range
10V
Voltage output
20mA
Current output
p5 Lower limit of span (specify using mV
or µA)
-10000 to 10000 (when p4 is 10 V)
0 to 20000 (when p4 is 20 µA)
p6 Lower limit of span (specify using mV
or µA)
-10000 to 10000 (when p4 is 10 V)
0 to 20000 (when p4 is 20 mA)
p7 Preset value (specify using mV or µA)
-11000 to 11000 (for voltage output)
0 to 22000 (for current output)
p8 Reference channel
001 to 060 or A001 to A300
1.4 Setting Commands (System Related)