Wa modbus master settings, Wb modbus master command settings – Yokogawa Standalone MW100 User Manual
Page 43
1-36
IM MW100-17E
Example
Set command number to 003, command to valid,
command type to READ, server number to 1, register
address to 30001, data type to INT16, first channel to
C001, last channel to C005, and unit number to 1.
WF003,ON,READ,1,30001,INT16,C001,C005,1
Explanation • You can set this command on products with the /M1
MATH function option.
• When p3 is READ, p7 and p8 can only be set to
C001 to C003.
• p7 and p8 can only be set to the same type of
channel.
• If the data type is INT16 or UNIT16, the maximum
number of channels that can be set from first to last
channel is 127. For other data types, the maximum
is 63.
• Command to specify the unit number
Firmware version R3.03 or earlier: WE
Firmware version R3.04 or later: WF
See the note below.
Note
The "Unit number" parameter of the WE command under the
firmware version R3.03 has been changed to the WF command
under firmware version R3.04. If settings files are loaded that are
of older or newer version than the firmware version, any extra or
missing parameters will be ignored or added when the settings
are interpreted. For example, users not connected to Modbus
Gateway (users using unit number 255) can obtain the same
operational result even if they load settings files of older or newer
versions. However, users connected to Modbus Gateway (users
using unit numbers other than 255) will have to manually reenter
the unit numbers after loading the settings file.
If an R3.04 or later settings file is loaded with firmware version
R3.03 or earlier
Settings (Firmware version
R3.04 or later)
Interpreted (Firmware
version R3.03 or earlier)
WE01,modbus.server.
com,502
WE01,modbus.server.
com,502,255
The underlined portion is
added to the previous settings.
WF001,ON,READ,01,30001
,INT16,C001,C001,255
WF001,ON,READ,01,30001
,INT16,C001,C001
The underlined parameter is
ignored.
If an R3.03 or earlier settings file is loaded with firmware version
R3.04 or later
Settings (Firmware version
R3.03 or earlier)
Interpreted (Firmware
version R3.04 or later)
WE01,modbus.server.
com,502,255
WE01,modbus.server.
com,502
The underlined parameter is
ignored.
WF001,ON,READ,01,30001
,INT16,C001,C001
WF001, ON,READ,01,3000
1,INT16,C001,C001,255
The underlined portion is
added to the previous settings.
WA
Modbus Master Settings
Setting
WAp1,p2,p3,p4,p5
p1 Communication interval
100mS/200mS/250mS/500mS
1S/2S/5S/10S/20S/30S/40S/50S/60S/90S/
120S
p2 Communication timeout
100mS/200mS/250mS/500mS/1S
p3 Retry count (OFF/1 to 5)
p4 Communication recovery wait (0 to
120)[sec]
p5 Wait between commands (OFF/10 mS/20
mS/50 mS/100 mS)
Query
WA?
Example
Set the communication interval to 500 ms, the
communication timeout to 250 ms, number of retries to
2, communication recovery wait to 30 seconds, and the
gap between commands to 50 ms.
WA500mS,250mS,2,30,50mS
Explanation You can set this command on products with the /M1
MATH function option.
WB
Modbus Master Command
Settings
Setting
When p2=OFF
WBp1,p2
When p2=ON
WBp1,p2,p3,p4,p5,p6,p7,p8
p1 Command number (001 to 100)
p2 Command valid/invalid (ON/OFF)
p3 Command types
READ
Load value from Modbus
register of other
instrument.
WRITE
Write value to Modbus
register of other instrument
p4 Slave address (1 to 247)
p5 Register address
For p3=READ
00001 to 09999 (Firmware version
R3.04 or later)
10001 to 19999 (Firmware version
R3.04 or later)
100001 to 165535 (Firmware version
R3.04 or later)
30001 to 39999
300001 to 365535
40001 to 49999
400001 to 465535
For p3=WRITE
00001 to 09999 (Firmware version
R3.04 or later)
40001 to 49999
400001 to 465535
1.6 Setting Commands (Communication Related)