IM MW100-17E

LIMIT

*1

Continue the computation by

replacing the overflow value
with upper or lower limit value

*1 The upper or lower limit value that is replaced for

the measurement input channel varies depending
on the MATH type.

Measurement input

channel

Upper/lower limit of

the measuring range

Scaled measurement

input channel

Upper/lower limit of

scaling

p4 Sum scale of the TLOG.SUM computation
OFF

Sum value of the data for
each measurement interval

SEC

Sum value of the data for each
measurement interval/number of
computations per second

MIN

Sum value of the data for each
measurement interval/number of
computations per minute

HOUR

Sum value of the data for each
measurement interval/number of
computations per hour

DAY

Sum value of the data for
each measurement interval/
number of computations per
day (Firmware version R3.03
or later)

p5 Special MATH processing when the

input value of the measurement input
channel is in error in a TLOG or CLOG
computation

*2

ERROR

Sets the computed value to
MATH error.

SKIP

Continue the computation using
the previous value ignoring
the input value in error

p6 Special MATH processing when the

input value of the measurement input
channel is overflow in a TLOG or CLOG
computation

*2

ERROR

Sets the computed value to
MATH error.

SKIP

Computed value is ignored
and computation continues

LIMIT

*3

Apply input to upper or

lower limit value and
continue computation

*2 For details, see the MW100 Data Acquisition Unit

User’s Manual (IM MW100-01E).

*3 The upper or lower limit value that is replaced for

the reference channel varies depending on the
MATH type.

Measurement input

channel

Upper/lower limit of

the measuring range

Scaled measurement

input channel

Upper/lower limit of

scaling

MATH channel

Upper/lower limit of

span

p7 Overflow processing of TLOG.PSUM

computation

OVER

Stop the computation as
overflow when 99999999 is
exceeded

ROTATE Continue the computation by

resetting the count to 0 when
99999999 is exceeded

Query

XG?

Example

Set operation upon MATH error to +OVER, operation
upon abnormality in computation other than CLOG/
TLOG to SKIP, overflow operation for other than CLOG/
TLOG to SKIP, time scaling for TLOG.SUM computation
to units of minutes, operation upon abnormal input
from CLOG/TLOG computation to ERROR, operation
upon CLOG/TLOG computation overflow to LIMIT,
and operation upon TLOG.PSUM computation over to
OVER.

XG+OVER,SKIP,SKIP,MIN,ERROR,LIMIT,OVER

Explanation You can set this command on products with the /M1

MATH function option, and when the pulse input module
is installed.

MC

File Message Settings

Setting

MCp1,p2
p1 File message type
MESSAGE

For recording

MESSAGE_T For thinning recording
p2 Message string (up to 120 characters)

Query

MC?

Explanation • This command sets a common message to all files in

the recording interval (between record start to record
stop).

• There are two message types: recording and

thinning recording. The recorded message is
common to measurement groups 1 to 3 and MATH
and does not depend on the record start timing.

• For the characters that can be used for the

messages, see “User Specified Strings” in section
1.3.

• You cannot change the settings while recording.

MD

Data Save Folder Settings

Setting

MDp1,p2,p3
p1 Type
AUTO

Auto generation

PARTIAL Partial setting
FREE

Arbitrary string

DATE

Date and time

p2 Folder name (1 to 8 characters)
p3 Start number (0 TO 9999)

Query

MD?

1.4 Setting Commands (System Related)