Yokogawa Standalone MW100 User Manual
Page 122
App-20
IM MW100-17E
Display Possible Problem
Corrective Action
E040 Invalid client type.
Enter a correct client type.
E041 Invalid server type.
Enter a correct server type.
E050 Invalid input type.
Enter an input type that can be selected for the module specified by
the channel number.
E051 Module of an invalid input type found in the
Enter an input type that can be selected for all modules specified
range of specified channels.
by the channel range.
E052 Invalid measuring range.
Enter a measurement range that can be selected for the module
specified by the channel number.
E053 Module of an invalid measuring range found in
Enter a measurement range that can be selected for all modules
the range of specified channels.
specified by the channel range.
E054 Upper and lower limits of span cannot be equal. Set a different value for the upper and lower limits of span.
E055 Upper and lower limits of scale cannot be equal. Set a different value for the upper and lower limits of scale.
E056 Invalid reference channel number.
Set channels other than the input module’s own channel.
E060 Cannot set an alarm for a skipped channel.
Set a type for the channel number setting other than SKIP.
E061 Cannot set an alarm for a channel on which
Set the ON/OFF setting for expressions on the channel number
MATH function is turned OFF.
to ON.
E062 Invalid alarm type.
Enter an allowed alarm type.
E063 Invalid alarm relay number.
Set a relay number for alarm output relays.
E065 Cannot set hysteresis for a channel on which
Set the channel number alarm type to something other than OFF.
alarm are turned OFF
E070 Nonexistent channel specified in MATH
Check whether a channel number outside of the allowable range
expression.
was specified in the expression.
E071 Nonexistent constant specified in MATH
Check whether a MATH constant outside of the allowable range
expression.
was specified in the expression.
E072 Invalid syntax found in MATH expression.
Check whether the syntax of the expression is correct.
E073 Too many operators for MATH expression.
Reduce the number of operators.
E074 Invalid order of operators.
Check whether the relationship between the operators used in the
expression satisfies proper syntax.
E075 Upper and lower limits of MATH span cannot be Set a different value for the upper and lower limits of the MATH
equal.
span.
E080 Incorrect MATH group format.
Check whether the MATH group format is correct.
E081 Incorrect channels for MATH group.
Check whether there are any channels outside the allowable range
specified in the MATH group.
E082 Too many channels for MATH group.
Reduce the number of channels specified in the MATH group.
E090 Incorrect break point format.
Use the correct break point format.
E091 Time value of break point exceeds the setting
Set a time within the allowable range.
range.
E092 Output value of break point exceeds the setting Set an output value within the allowable range.
range.
E093 No break point found.
Set one or more break points.
E094 Invalid time value of first break point.
Set the time of break point 1 to zero.
E095 Invalid time sequence found in break points.
Set the times of break points in ascending order.
E100 Invalid output type.
Enter an output type that can be selected for the module specified
by the channel number.
E101 Modul of an invalid output type found in the
Enter an output type that can be selected for all
range of specified channels.
modules specified by the channel range.
E102 Invalid output range.
Enter an output range that can be selected for the module specified
by the channel number.
E103 Module of an invalid output range found in the
Enter an output type that can be selected for all
range of specified channels.
modules specified by the channel range.
E104 Upper and lower limits of output span cannot
Set a different value for the upper and lower limits of output span.
be equal.
E105 Invalid transmission reference channel.
Set a channel number of the input module or a MATH channel
number.
E110
Invalid channel number for contact input event.
Set the channel number for the universal input module or DI module.
Appendix 7 Error Display on the 7-Segment LED and Corrective Actions