1.4 Setting Commands
(System Related)
SR
Input Range Settings
Setting
When p2=SKIP
SRp1,p2
When p2=RRJC
SRp1,p2,p3,p4,p5,p6
When p2=VOLT, TC, RTD, DI, OHM, STR, or PULSE
When p6=OFF
SRp1,p2,p3,p4,p5,p6
When p6=DELTA
SRp1,p2,p3,p4,p5,p6,p7
When p6=SCALE
SRp1,p2,p3,p4,p5,p6,p7,p8,p9,p10
When Setting SKIP
Setting
SRp1,p2
p1 Channel range (001 to 060)
p2 Input type (SKIP)
Query
SR[p1]?
Example
Skip channel 1.
SR001,SKIP
Explanation • Channels set to SKIP are not measured.
• Specify measurement channels for p1.
When Setting RRJC
Setting
SRp1,p2,p3,p4,p5,p6
p1 Channel range (001 to 060)
p2 Input type (RRJC)
RRJC Remote RJC
p3 Measuring range (specify thermocouple
range)
p4 Lower limit of span
p5 Upper limit of span
p6 Reference channel number (001 to 060)
Query
SR[p1]?
Example
Set the measuring range on channel 2 to K, lower limit
of span to 0.0°C, upper limit of span to 500.0°C, and
set channel 1 (reference channel) as the remote RJC
reference channel.
SR002,RRJC,K,0,5000,001
Explanation • Set the p3, p4, and p5 setting parameters according
to the table in section 1.3.
• The decimal place is fixed as shown in the table in
section 1.3.
• Specify measurement channels on p1.
When Setting Voltage, TC, RTD, Contact,
Resistance, Strain Input, and Pulse
• With no MATH
Setting
SRp1,p2,p3,p4,p5,p6
p1 Channel range (001 to 060)
p2 Input type
VOLT
DC voltage
TC
Thermocouple
RTD
Resistance temperature
detector
DI
Contact
OHM
Resistance
STR
Strain
PULSE
Pulse
p3 Measuring range
p4 Lower limit of span
p5 Upper limit of span
p6 MATH type (OFF)
Query
SR[p1]?
Example
Set the input type for channels 1 to 4 to TC type R, the
lower limit span to 0.0°C, and the upper limit of span to
1760.0°C.
SR001-004,TC,R,0,17600,OFF
Explanation Specify measurement channels for p1.
• When Setting Difference Computation between
Channels
Setting
SRp1,p2,p3,p4,p5,p6,p7
p1 Channel range (001 to 060)
p2 Input type
VOLT
DC voltage
TC
Thermocouple
RTD
Resistance temperature
detector
DI
Contact input
OHM
Resistance input
STR
Strain input
PULSE
Pulse
p3 Measuring range
p4 Lower limit of span
p5 Upper limit of span
p6 MATH type (DELTA)
p7 Reference channel numbers (001 to
060)
Query
SR[p1]?
Example
Set the MATH type for channel 10 to difference
computation between channels with channel 1 (the
reference channel), set the input type to TC, measuring
range to R, the lower limit span to 10.0°C, and the
upper limit of span to 100.0°C.
SR010,TC,R,100,1000,DELTA,001
Explanation Specify measurement channels on p1.
1.4 Setting Commands (System Related)