beautypg.com

4 setting commands (system related), Setting commands (system related) -16, Sr input range settings – Yokogawa Standalone MW100 User Manual

Page 23

background image

1-16

IM MW100-17E

1.4 Setting Commands

(System Related)

SR

Input Range Settings

Setting

When p2=SKIP

SRp1,p2

When p2=RRJC

SRp1,p2,p3,p4,p5,p6

When p2=VOLT, TC, RTD, DI, OHM, STR, or PULSE

When p6=OFF

SRp1,p2,p3,p4,p5,p6

When p6=DELTA

SRp1,p2,p3,p4,p5,p6,p7

When p6=SCALE

SRp1,p2,p3,p4,p5,p6,p7,p8,p9,p10

When Setting SKIP

Setting

SRp1,p2
p1 Channel range (001 to 060)
p2 Input type (SKIP)

Query

SR[p1]?

Example

Skip channel 1.
SR001,SKIP

Explanation • Channels set to SKIP are not measured.

• Specify measurement channels for p1.

When Setting RRJC

Setting

SRp1,p2,p3,p4,p5,p6
p1 Channel range (001 to 060)
p2 Input type (RRJC)
RRJC Remote RJC
p3 Measuring range (specify thermocouple

range)

p4 Lower limit of span
p5 Upper limit of span
p6 Reference channel number (001 to 060)

Query

SR[p1]?

Example

Set the measuring range on channel 2 to K, lower limit
of span to 0.0°C, upper limit of span to 500.0°C, and
set channel 1 (reference channel) as the remote RJC
reference channel.
SR002,RRJC,K,0,5000,001

Explanation • Set the p3, p4, and p5 setting parameters according

to the table in section 1.3.

• The decimal place is fixed as shown in the table in

section 1.3.

• Specify measurement channels on p1.

When Setting Voltage, TC, RTD, Contact,

Resistance, Strain Input, and Pulse

• With no MATH

Setting

SRp1,p2,p3,p4,p5,p6
p1 Channel range (001 to 060)
p2 Input type
VOLT

DC voltage

TC

Thermocouple

RTD

Resistance temperature
detector

DI

Contact

OHM

Resistance

STR

Strain

PULSE

Pulse

p3 Measuring range
p4 Lower limit of span
p5 Upper limit of span
p6 MATH type (OFF)

Query

SR[p1]?

Example

Set the input type for channels 1 to 4 to TC type R, the
lower limit span to 0.0°C, and the upper limit of span to
1760.0°C.
SR001-004,TC,R,0,17600,OFF

Explanation Specify measurement channels for p1.

• When Setting Difference Computation between

Channels

Setting

SRp1,p2,p3,p4,p5,p6,p7
p1 Channel range (001 to 060)
p2 Input type
VOLT

DC voltage

TC

Thermocouple

RTD

Resistance temperature
detector

DI

Contact input

OHM

Resistance input

STR

Strain input

PULSE

Pulse

p3 Measuring range
p4 Lower limit of span
p5 Upper limit of span
p6 MATH type (DELTA)
p7 Reference channel numbers (001 to

060)

Query

SR[p1]?

Example

Set the MATH type for channel 10 to difference
computation between channels with channel 1 (the
reference channel), set the input type to TC, measuring
range to R, the lower limit span to 10.0°C, and the
upper limit of span to 100.0°C.
SR010,TC,R,100,1000,DELTA,001

Explanation Specify measurement channels on p1.

1.4 Setting Commands (System Related)