App index, Xv measurement interval settings, Vm math interval settings – Yokogawa Standalone MW100 User Manual
Page 32: Xg settings of operation upon math error
1-25
IM MW100-17E
Commands
1
2
3
App
App
Index
When Starting Match Time in Units of Weeks
Setting
SQp1,p2,p3,p4
p1 Match time number (1 to 3)
p2 Start type (WEEK)
p3 Start Date/time-day of week
SUN Sunday
MON Monday
TUE Tuesday
WED Wednesday
THU Thursday
FRI Friday
SAT Saturday
p4 Start date/time-time (HH:MM)
HH hours (00 to 23)
MM
Minute (00 to 59)
Query
SQ[p1]?
Example
Set match time number 1 to Friday, 17 hours 30
minutes.
SQ1,WEEK,FRI,17:30
When Starting Match Time in Units of One Day
Setting
SQp1,p2,p3
p1 Match time number (1 to 3)
p2 Start type (DAY)
p3 Start date/time-time (HH:MM)
HH hours (00 to 23)
MM
Minute (00 to 59)
Query
SQ[p1]?
Example
Set match time number 1 to 17 hours 30 minutes.
SQ1,DAY,17:30
XV
Measurement Interval Settings
Setting
XVp1,p2
p1 Measurement group number (1 to 3)
p2 Measurement interval
OFF
10mS/50mS/100mS/200mS/500mS
(miliseconds)
1S/2S/5S/10S/20S/30S/60S (seconds)
Query
XV[p1]?
Example
Set measurement group number 1 to a measurement
interval of 1 second.
XV1,1S
XI
Measurement Groups and A/D
Integration Time Settings
Setting
XIp1,p2,p3
p1 Module number (0 to 5)
p2 Measurement group number (OFF, 1 to
3)
p3 A/D integration time
(AUTO, 50 Hz, 60 Hz)
Query
XI[p1]?
Example
Set module number 0 to measurement group 1 and A/D
integration time to automatic detection.
XI0,1,AUTO
Explanation • If the module specified in p1 has a shortest
measurement interval of 100 ms, you cannot set
measurement group numbers having measurement
intervals of 10 ms or 50 ms. Also, if the module has
a shortest measurement interval of 500 ms, you
cannot set measurement group numbers having
measurement intervals of 10 ms, 50 ms, or 100 ms.
• Measurement group numbers cannot be specified for
output modules and unmounted modules.
• For the 30-CH Medium Speed DCV/TC/DI Input
Module, enter the same settings for the three
measurement groups and A/D integral times.
VM
MATH Interval Settings
Setting
VMp1
p1 Measurement group number
(OFF, 1 to 3)
Query
VM?
Example
Set MATH interval to measurement group number 1.
VM1
Explanation • You can set this command on products with the /M1
MATH function option, and when the pulse input
module is installed.
• Measurement group numbers of measurement
interval 10 ms or 50 ms cannot be set.
XG
Settings of Operation upon
MATH Error
Setting
XGp1,p2,p3,p4,p5,p6,p7
p1 Operation upon Math Error
+OVER
Set computed value to +Over
-OVER
Set computed value to -Over
p2 Special MATH processing when the
input value of the measurement input
channel is in error in a computation
other than TLOG and CLOG.
ERROR
Sets the computed value to
MATH error.
SKIP
Continue the computation
using the previous value for
channels with an error in
the input value.
p3 Special MATH processing when the
input value of the measurement input
channel is overflow in a computation
other than TLOG and CLOG.
ERROR
Compute using the overflow
value
SKIP
Continue the computation using
the previous value for channels
with an overflow value
1.4 Setting Commands (System Related)