beautypg.com

Sk math constant settings, Mg math group settings, Ro report operation and creation time settings – Yokogawa Standalone MW100 User Manual

Page 27: Rm report execution channel settings

background image

1-20

IM MW100-17E

• Enter setting parameters for p4, p5 excluding the

decimal place.

• If p1 is set to a MATH channel between A061

and A300, you can specify four arithmetic
operations or MATH constants in p3 in addition to
a communication input channel between C001 and
C300.

• For the characters that can be used for p7, see user

specified characters in section 1.3.

SK

MATH Constant Settings

Setting

SKp1,p2
p1 Channel range (K01 to K60)
p2 MATH constants

Query

SK[p1]?

Example

Set MATH constant K01 to 1.0000E-10.
SKK01,1.0000E-10

Explanation • You can set this command on products with the /M1

MATH function option.

• See section 1.3 for the setting range for MATH

constants.

MG

MATH Group Settings

Setting

MGp1,p2
p1 MATH group number (1 to 7)
p2 Channel structure (up to 36

characters)

(A001 to A060)

Query

MG[p1]?

Example

Set MATH group number 1 to channels A001 to A003.
MG1,A001-A003

Explanation • You can set this command on products with the

/M1 MATH function option, or when the pulse input
module is installed.

• See section 1.3 for the channel setting method.

Note that the channels that can be input are A001 to
A060.

RO

Report Operation and Creation

Time Settings

Setting

When p1=OFF
ROp1
When p1=ON
ROp1,p2,p3,p4,p5,p6,p7
p1 Report operation (OFF/ON)
p2 Reset data when recording starts
ON

Reset

OFF

Do not reset

p3 Time to create daily, weekly, and

monthly reports

hh

Hour (00 to 23)

p4 Day of week to create weekly report
SUN

Sunday

MON

Monday

TUE

Tuesday

WED

Wednesday

THU

Thursday

FRI

Friday

SAT

Saturday

p5 Date to create monthly report
dd

Date (1 to 28)

p6 Handling of abnormal input values

for maximum, minimum, integral, or
average values

ERROR

The report data is “ Error”

SKIP

Ignore the abnormal input
value and use the previous
value

p7 Handling of overflow values for

integral/average values

ERROR

The report data is “ Error”

SKIP

Ignore the overflow value
and use the previous value

LIMIT

*1

The overflow value is

replaced with the upper or
lower limit

*1 The lower/upper limit value replaced differs

depending on the channel’s setting condition.

Measurement input

channel

Measurement range

upper and lower limit

Scaled measurement

input channel

Upper and lower limit

of scaling

MATH channel

Upper/lower limit of

span

Query

RO?

Example

Set the following: Resetting upon recording start and
report operation: ON; daily, weekly, and monthly reports:
hour = 0 am; weekly reports: Monday; create monthly
reports on the 1st; abnormal input value: ERROR;
overflow values: ERROR.
ROON,ON,00,MON,01,ERROR,ERROR

Explanation • You can set this command on products with the /M3

report function option.

• The hour on which daily, weekly, and monthly reports

are created is the same for all.

RM

Report Execution Channel

Settings

Setting

When p2=OFF
RMp1,p2
When p2=ON
RMp1,p2,p3,p4,p5
p1 Box number (01 to 60)
p2 Use/do not use box (OFF/ON)
p3 Channel range (001 to 060 and A001 to

A300)

p4 Unit of time for integration
OFF The integral value of the data

from each measurement or MATH
interval

1.4 Setting Commands (System Related)