beautypg.com

Yokogawa Standalone MW100 User Manual

Page 129

background image

App-27

IM MW100-17E

Appendix

1

2

3

App

App

Index

When using RSLogix 500 with controllers such as the MicroLogix series that have on
board Ethernet support, the Setup Screen looks slightly different as instead of a Node
Address, direct input of the MW100 IP address is allowed (no gateway or DF1 to EIP
routing is required in this case).

Write Message as configured in a MicroLogix or SLC 505 with EIP support

An explicit message should be triggered on/off by some sort of logic; the following image
represents using the seconds bit of the PLC’s clock to activate the message.

Time Based Message Write

Appendix 8 Detailed Explicit and I/O Messaging using RSLogix