4 ai function block parameters, Table 5.15 indexes to view objects for each block – Yokogawa RotaMASS 3-Series User Manual
Page 40

5. CONFIGUrATION
5-16
IM 01R04B05-00E-E 3rd edition July 30, 2010 -00
all Rights Reserved. Copyright © 2005, Rota Yokogawa
T0515-2.EPS
41
FF_SCALE
11
42
FF_GAIN
4
43
UPDATE_EVT
44
BLOCK_ALM
45
ALARM_SUM
8
8
46
ACK_OPTION
2
47
ALARM_HYS
4
48
HI_HI_PRI
1
49
HI_HI_LIM
4
50
HI_PRI
1
51
HI_LIM
4
52
LO_PRI
1
53
LO_LIM
4
54
LO_LO_PRI
1
55
LO_LO_LIM
4
56
DV_HI_PRI
1
57
DV_HI_LIM
4
58
DV_LO_PRI
1
59
DV_LO_LIM
4
60
HI_HI_ALM
61
HI_ALM
62
LO_ALM
63
LO_LO_ALM
64
DV_HI_ALM
65
DV_LO_ALM
Total bytes
43
43
83
104
Relative
Index Parameter Mnemonic
VIEW
1
VIEW
2
VIEW
3
VIEW
4
Table 5.15 Indexes to View Objects for Each
Block
T0516.EPS
40420
40430
40410
40400
40432
40422
40431
40412
40200
40421
40411
40102
40401
40100
40101
40201
40423
AI4 block
AI3 block
40402
AI2 block
40413
40433
40403
40203
40202
Transducer block
AI1 block
Resource block
PID block (optional) 40800 40801
40802
40803
40103
VIEW
1
VIEW
2
VIEW
3
VIEW
4
B
lock
IT2 block
IT1 block
AI5 block
AI6 block
40440 40441
40442
40443
40450 40451
40452
40453
40600 40601
40602
40603
40610 40611
40612
40613
5.6.4 AI Function Block Parameters
Parameters of the six aI function blocks can be
read and written from the host. For a list of block
parameters in each RotaMaSS, refer to ap-
pendix 1, “List of Parameters for Each Block of
RotaMaSS.” the following describes important
parameters and how to set them. For a model
with an option adding a PID function block and
LM functionality, see appendixes 5 and 6.
MOdE_BLK:
Indicates the three types of function block
modes; out_of_Service, Manual, and auto. In
out_of_Service mode, the aI block does not
operate. the Manual mode does not allow val-
ues to be updated. the auto mode causes the
measured value to be updated. under normal
circumstances, set the auto mode to take ef-
fect. the auto mode is the factory default.
CHANNEL:
this is the parameter of the transducer block
to be input to the aI block. aI1 block is as-
signed mass flow rate. aI2 block is assigned
volume flow rate. aI3 block is asigned den-
sity. aI4 block is asigned temperature. aI5 is
assigned concentration measurement. aI 6 is
assigned net flow rate. Do not change this set-
ting.
Xd_SCALE:
Scale of input from the transducer block.
Changing the unit (can be set only in mass
flow rate) also causes the unit within the trans-
ducer block to be automatically changed. (the
unit is automatically changed according to the
unit selected by aI 1, 2, 3, 4, 5, 6. aI5.XD_
SCaLE.unIt_InDEX depend on customer’s
spec.) units which can be set by XD_SCaLE
are shown table 5.16.
note: With the same setting, some units are represented
differently between the F
ounDatIon
Fieldbus com-
munication type and the HaRt communication type of
a RotaMaSS. Each unit enclosed in brackets above
shows the unit for the HaRt communication type of
RotaMaSS corresponding to the preceding unit (for
the Foundation Fieldbus communication type).