5. CONFIGUrATION

5-16

IM 01R04B05-00E-E 3rd edition July 30, 2010 -00

all Rights Reserved. Copyright © 2005, Rota Yokogawa

T0515-2.EPS

41

FF_SCALE

11

42

FF_GAIN

4

43

UPDATE_EVT

44

BLOCK_ALM

45

ALARM_SUM

8

8

46

ACK_OPTION

2

47

ALARM_HYS

4

48

HI_HI_PRI

1

49

HI_HI_LIM

4

50

HI_PRI

1

51

HI_LIM

4

52

LO_PRI

1

53

LO_LIM

4

54

LO_LO_PRI

1

55

LO_LO_LIM

4

56

DV_HI_PRI

1

57

DV_HI_LIM

4

58

DV_LO_PRI

1

59

DV_LO_LIM

4

60

HI_HI_ALM

61

HI_ALM

62

LO_ALM

63

LO_LO_ALM

64

DV_HI_ALM

65

DV_LO_ALM

Total bytes

43

43

83

104

Relative

Index Parameter Mnemonic

VIEW

1

VIEW

2

VIEW

3

VIEW

4

Table 5.15 Indexes to View Objects for Each
Block

T0516.EPS

40420

40430

40410

40400

40432

40422

40431

40412

40200

40421

40411

40102

40401

40100

40101

40201

40423

AI4 block

AI3 block

40402

AI2 block

40413

40433

40403

40203

40202

Transducer block

AI1 block

Resource block

PID block (optional) 40800 40801

40802

40803

40103

VIEW

1

VIEW

2

VIEW

3

VIEW

4

B

lock

IT2 block

IT1 block

AI5 block
AI6 block

40440 40441

40442

40443

40450 40451

40452

40453

40600 40601

40602

40603

40610 40611

40612

40613

5.6.4 AI Function Block Parameters

Parameters of the six aI function blocks can be
read and written from the host. For a list of block
parameters in each RotaMaSS, refer to ap-
pendix 1, “List of Parameters for Each Block of
RotaMaSS.” the following describes important
parameters and how to set them. For a model
with an option adding a PID function block and
LM functionality, see appendixes 5 and 6.

MOdE_BLK:
Indicates the three types of function block

modes; out_of_Service, Manual, and auto. In
out_of_Service mode, the aI block does not
operate. the Manual mode does not allow val-
ues to be updated. the auto mode causes the
measured value to be updated. under normal
circumstances, set the auto mode to take ef-
fect. the auto mode is the factory default.

CHANNEL:
this is the parameter of the transducer block

to be input to the aI block. aI1 block is as-
signed mass flow rate. aI2 block is assigned
volume flow rate. aI3 block is asigned den-
sity. aI4 block is asigned temperature. aI5 is
assigned concentration measurement. aI 6 is
assigned net flow rate. Do not change this set-
ting.

Xd_SCALE:
Scale of input from the transducer block.

Changing the unit (can be set only in mass
flow rate) also causes the unit within the trans-
ducer block to be automatically changed. (the
unit is automatically changed according to the
unit selected by aI 1, 2, 3, 4, 5, 6. aI5.XD_
SCaLE.unIt_InDEX depend on customer’s
spec.) units which can be set by XD_SCaLE
are shown table 5.16.

note: With the same setting, some units are represented

differently between the F

ounDatIon

Fieldbus com-

munication type and the HaRt communication type of
a RotaMaSS. Each unit enclosed in brackets above
shows the unit for the HaRt communication type of
RotaMaSS corresponding to the preceding unit (for
the Foundation Fieldbus communication type).