A7.5.2 descriptions for LM Parameters

the following describes LM parameters of a
RotaMaSS transmitter.

notE: Do not turn off the power to the RotaMaSS for 60

seconds after making a change to its parameter set-
tings.

(1) dlmeLinkMasterCapabilitiesVariable

Meaning

Bit

Position

Value

Description

1


0


0

LaS Schedule
in non-volatile
Memory

Last Values
Record
Supported

Link Master
Statistics
Record
Supported

Whether the LaS schedule can
(= 1) or cannot (= 0) be saved
to the non-volatile memory

Whether to support (= 1) or not
to support (= 0)
LastValuesRecord.

Whether to support (= 1) or not
to support (= 0)
DlmeLinkMasterStatisticsRecord.

B3: 0x04

B2: 0x02

B1: 0x01

ta0606.EPS

(2) dlmeLinkMasterInforecord

Element

Sub-

index

Descrip-

tion

Size

[bytes]

1

2

2

2

2

4

2

2

V(MSo)

V(DMDt)

V(DtHt)

V(ttRt)

V(LtHt)

V(tDP)

V(MICD)

V(LDDP)

MaxSchedulingoverhead

DefMintokenDelegtime

DeftokenHoldtime

targettokenRottime

LinkMainttokHoldtime

timeDistributionPeriod

MaximumInactivitytoClaimLasDelay

LasDatabaseStatusSpduDistributionPeriod

1

2

3

4

5

6

7

8

ta0607.EPS

(3) PrimaryLinkMasterFlagVariable
Explicitly declares the LaS. Writing “true” (0xFF)
to this parameter in a device causes that de-
vice to attempt to become the LaS. However,
a request of writing “true” to this parameter in a
device is rejected if the value of the same param-
eter in any other device that has a smaller node
address within the same segment is true.

(4) LiveListStatusArrayVariable
a 32-byte variable, in which each bit represents
the status of whether a device on the same seg-
ment is live or not. the leading bit corresponds
to the device address 0x00, and final bit to 0xFF.
the value of LiveListStatusarrayVariable in the
case where devices having the addresses 0x10
and 0x15 in the fieldbus segment is shown below.

0x00 00 84 00 00 00 00 00 00 00 00 00 00 00

00 00 00 00 00 00 00 00 00 00

00 00 00 00 00 00 00 00

Bit correspondences: 0 0 0 0 0 0 0 0 0 0 0

0x00

0 0 0 0 0 1 0 0 0 0 1 0 0...

0x10

0x15

(5) MaxTokenHoldTimeArray
an 8- by 64-byte array variable, in which each set
of 2 bytes represents the delegation time (set as
an octet time) assigned to a device. the delega-
tion time denotes a time period that is given to a
device by means of a Pt message sent from the
LaS within each token circulation cycle.

the leading 2 bytes correspond to the device
address 0x00, and the final 2 bytes to the device
address 0xFF. Specify the subindex to access
this parameter.

(6) BootOperatFunctionalClass
Writing 1 to this parameter in a device and restart-
ing the device causes the device to start as a
basic device. on the contrary, writing 2 to this
parameter and restarting the device causes the
device to start as an LM.

(7) CurrentLinkSettingrecord and Config-

uredLinkSettingsrecord

CurrentLinkSettingRecord indicates the bus pa-
rameter settings currently used. ConfiguredLink-
SettingsRecord indicates the bus parameter
settings to be used when the device becomes the
LaS. thus, when a device is the LaS, its Cur-
rentLinkSettingRecord and ConfiguredLinkSetting-
sRecord have the same values.

Element

Sub-

index

Descrip-

tion

Size

[bytes]

2

1

1

1

2

1

1

1

1

1

1

V(St)

V(PhLo)

V(MRD)

V(Fun)

V(tL)

V(MID)

V(nun)

V(PhPE)

V(PhGE)

V(PhIS)

V(tSC)

Slottime

PerDlpduPhloverhead

MaxResponseDelay

FirstunpollednodeId

thisLink

MinInterPduDelay

numConsecunpollednodeId

PreambleExtension

PosttransGapExtension

MaxInterChanSignalSkew

timeSyncClass

1

2

3

4

5

6

7

8

9

10

11

ta0608.EPS