Yokogawa RotaMASS 3-Series User Manual
Page 144

APPENdIX 3. OPErATION OF EACH PArAMETEr IN FAILUrE MOdE
a-44
IM 01R04B05-00E-E 3rd edition July 30, 2010 -00
all Rights Reserved. Copyright © 2005, Rota Yokogawa
2. Alarm Mask Switch Settings
Some alarms can be disabled and enabled us-
ing switches in parameter aLaRM_PERFoRM
inside the transducer block as explained below.
(1) Setting
as shown in the following table, the indi-
vidual bits of aLaRM_PERFoRM at relative
index 125 act as switches to disable and
enable particular alarms. Write zeros to the
respective bits to disable desired alarms, or
write ones to enable them.
(2) default Values
See the table below. .
TA0303.EPS
unused bit
unused bit
unused bit
unused bit
unused bit
unused bit
unused bit
PID
IT2
IT1
AI6
AI5
AI4
AI3
AI2(A-24,W-22,W-42,W52)
AI1(A-23,W-21,W-41,W51)
Factory Default
(0 = Disable; 1 = Enable)
Bit 15
Bit 14
Bit 13
Bit 12
Bit 11
Bit 10
Bit 9
Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Bit in ALARM_PERFORM
Corresponding Alarms
0
0
0
0
0
0
0
0
0
0
0
0
0
these default bit statuses comprise 0xxxxx as the default value of aLaRM_PERFoRM