beautypg.com

A5.7 control action by- pass, A5.8 feed-forward, A5.9 block modes – Yokogawa RotaMASS 3-Series User Manual

Page 151

background image

APPENdIX 5. PId BLOCK

a-51

IM 01R04B05-00E-E 3rd edition July 30, 2010 -00

all Rights Reserved. Copyright © 2005, Rota Yokogawa

A5.7 Control Action By-

pass

the PID control computation can be bypassed
so as to set the SP value in the control output
out as shown below. Setting BYPaSS to “on”
bypasses the PID control computation.

Setpoint

Control

Feed-

forward

CaS_In

Filter

In

PV

BYPaSS

SP

RCaS_In

output

out

Fa0502.EPS

A5.8 Feed-forward

Feed-forward is an action to add a compensa-
tion input signal FF_VaL to the output of the PID
control computation, and is typically used for feed-
forward control. the following figure illustrates the
action.

PID

computation

FF_SCaLE

out_SCaLE

PV

out

FF_VaL

FF_GaIn

Fa0503.EPS

A5.9 Block Modes

the block mode is set in the parameter MoDE_
BLK.

Stipulates the target mode to which the
PID block transfers.

Indicates the current mode of the PID
block.

Stipulates all the modes that the PID
block can enter. the PID block is
prohibited to enter any mode other than
those set in this element.

Stipulates the mode in which the PID
block normally resides.

MoDE_
BLK

target

actual

Permitted


normal

ta0505.EPS

there are eight modes for a PID block as shown
below.

Block

Mode

Description

Remote output mode, in which the PID block outputs
the value set in Rout_In.

Remote cascade mode, in which the PID block
carries out the PID control computation based on the
setpoint (SP) set via the remote cascade connection,
such as from a computer, and outputs the computed
result.

Cascade mode, in which the PID block carries out the
PID control computation based on the setpoint (SP)
set from another fieldbus function block, and outputs
the computed result.

the PID block carries out automatic control and
outputs the result computed by the PID control
computation.

Manual mode, in which the PID block outputs the
value set by the user manually.

the PID block outputs the value set in tRK_VaL.

Initialization and manual mode, in which the control
action is suspended. the PID block enters this mode
when the specified condition is met
(see Section a5.14).

out of service mode, in which neither the control
computation nor action is carried out, and the output
is kept at the value that was output before the PID
block entered into o/S mode.

Rout

RCas



Cas


auto

Man

Lo

IMan


o/S

ta0506.EPS