A-14 – Yokogawa RotaMASS 3-Series User Manual
Page 114

APPENdIX 1. LIST OF PArAMETErS FOr EACH BLOCK OF rOTAMASS
a-14
IM 01R04B05-00E-E 3rd edition July 30, 2010 -00
all Rights Reserved. Copyright © 2005, Rota Yokogawa
relative
Index
Index
Parameter Name
Factory default
Write
Mode
Explanation
113
2113
CoRRoSIon_DaMP
10 h
o/S
Indicates the corrosion damping time.
When the value of CoRRoSIon_aLM_SEL
is “not apply”, users cannot change this
value. Range to 0 to 10 hours.
114
2114
FLuID_MaX_tEMP
0.0
-
this parameter indicates the maximum
reached fluid temperature since the last
reset.
user cannot reset this value, only in service.
115
2115
SELF_tESt
not Execute
o/S
a user can execute the SELF_tESt function
by this parameter. after executing the ERR_
StatuS, aLM_StatuS and WaRnG_
StatuS parameter will be updated.
116
2116
InItIaLIZE_EEPRoM
not Execute
o/S
a user can execute the initialization of EEP-
RoM by this parameter.
after a user enters a password, parameters
return to default values.
117
2117
ERR_StatuS
-
-
this parameter indicates the actual error
situation in RCCt3/FB.
118
2118
aLM_StatuS
-
-
this parameter indicates the actual alarm
situation in RCCt3/FB.
119
2119
WaRnG_StatuS
-
-
this parameter indicates the actual warning
situation in RCCt3/FB.
120
2120
HISt_oRD
-
-
this parameter indicates the last 10 errors,
alarms, warning events/status in their order
of occurrences.
the oldest will be removed after an 11th
occur (first in-first out function).
this parameter can be cleared by CLEaR_
HISt Parameter.
121
2121
HISt_aBS_ERR
-
-
this parameter indicates all error events/
status absolute after occurrences.
this parameter can be cleared by CLEaR_
HISt.
122
2122
HISt_aBS_aLM
-
-
this parameter indicates all alarm events/
status absolute after occurrences.
this parameter can be cleared by CLEaR_
HISt parameter.
123
2123
HISt_aBS_WaRnG
-
-
this parameter indicates all warning events/
status absolute after occurrences.
this parameter can be cleared by CLEaR_
HISt parameter.
124
2124
CLEaR_HISt
not Execute
o/S
this parameter clear entries in the HISt_oRD,
HISt_aBS_ERR, HISt_aBS_aLM, and
HISt_aBS_WaRnG parameter.
125
2125
aLaRM_PERFoRM
-
-
this parameter clears alarm/Warning
information about each function block,
temporarily.
If a user writes 0 to a/some with this param-
eter, the corresponding alarm and warning
will be cleared.
126
2126
aLaRM_SuM
0
-
the parameter shows current alarm.
127
2127
REFEREnCE_tEMPERatuRE
25°C
o/S
Indicates the temperature where the
reference density of both components of the
mixture has been determined.
128
2128
REFEREnCE_DEnSItY_CaRRIER 0.997039 kg/l
o/S
Indicates the density of the carrier liquid de-
termined at the reference temperature.
129
2129
tEMP_CoEFF_a_CaRRIER
-0.261 E-3/K
o/S
Indicates the linear temperature
coefficient of the density of the carrier liquid.
130
2130
tEMP_CoEFF_B_CaRRIER
-0.36 E-5/K²
o/S
Indicates the quadratic temperature coefficient
of the density of the carrier liquid.
131
2131
REFEREnCE_DEnSItY_PRoDuCt 0.0 kg/l
o/S
Indicates the density of the product
determined at the reference temperature.
132
2132
tEMP_CoEFF_a_PRoDuCt
0.0 E-3/K
o/S
Indicates the linear temperature
coefficient of the density of the product.
133
2133
tEMP_CoEFF_B_PRoDuCt
0.0 E-5/K
2
o/S
Indicates the quadratic temperature coefficient
of the density of the product.