APPENdIX 5. PId BLOCK
a-56
IM 01R04B05-00E-E 3rd edition July 30, 2010 -00
all Rights Reserved. Copyright © 2005, Rota Yokogawa
When configuring a simple PID control loop by
combining a RotaMaSS with a fieldbus valve
positioner that contains an ao block, follow the
procedure below to make the settings of the cor-
responding fieldbus function blocks:
1. Connect the aI block and PID block of the
RotaMaSS, and the ao block of the valve
positioner as shown above.
2. Set MoDE_BLK.target of the PID block to o/S,
and then set GaIn, RESEt, and RatE to ap-
propriate values.
3. Check that the value of MoDE_BLK.actual of
the aI block is auto.
4. Set MoDE_BLK.target of the ao block to
CaS|auto (meaning "CaS and auto").
5. Check that the value of BKCaL_In.status of the
PID block is not Bad.
6. Check that the value of In.status of the PID
block is not Bad.
7. Check that auto is set in MoDE_BLK.permit-
ted of the PID block.
8. Set MoDE_BLK.target of the PID block to
auto.
When finishing all steps in order, the PID block
and ao block exchange the respective informa-
tion and initialize the cascade connection. Con-
sequently, the value of MoDE_BLK.actual of the
PID block changes to auto and automatic PID
control starts.