APPENdIX 1. LIST OF PArAMETErS FOr EACH BLOCK OF rOTAMASS
a-12
IM 01R04B05-00E-E 3rd edition July 30, 2010 -00
all Rights Reserved. Copyright © 2005, Rota Yokogawa
relative
Index
Index
Parameter Name
Factory default
Write
Mode
Explanation
91
2091
FtC1
*)
o/S
Defines a linear temperature coefficient of
the frequency at roh = 1.
the valid range and the default value de-
pend on the selected sensor model.
92
2092
FtCK
*)
o/S
Defines a quadratic temperature coefficient
of the frequency at roh = 1.
the valid range and the default value de-
pend on the selected sensor model.
93
2093
SKP
*)
o/S
Defines a linear pressure coefficient of the
sensor constant SK20.
the valid range and the default value de-
pend on the selected sensor model.
94
2094
FPC
*)
o/S
Defines a linear pressure coefficient of the
frequency.
the valid range and the default value de-
pend on the selected sensor model.
95
2095
SKtK
*)
o/S
Defines a quadratic temperature coefficient
of the sensor constant SK20.
the valid range and the default value de-
pend on the selected sensor model.
96
2096
SKPt
*)
o/S
Defines a quadratic pressure coefficient of
the sensor constant SK20.
the valid range and the default value de-
pend on the selected sensor model.
97
2097
FPtC
*)
o/S
Defines a temperature - pressure coefficient
of the frequency.
the valid range and the default value de-
pend on the selected sensor model.
98
2098
FQC1
*)
o/S
Defines a linear flow coefficient of the fre-
quency.
the valid range and the default value de-
pend on the selected sensor model.
99
2099
FQC2
*)
o/S
Defines a quadratic flow coefficient of the
frequency.
the valid range and the default value de-
pend on the selected sensor model.
100
2100
PRESSuRE
0.0 bar
o/S
Sets the pressure value for correction with
SKP and FPC.
101
2101
PRESSuRE_unIt
bar
o/S
this parameter shows the unit of
PRESSuRE; range bar or psi.
102
2102
SLuG_aLaRM_SELECt
not apply
o/S
this parameter enables the following functions.
DRIVE_GaIn,
SLuG_CRItERIa
SLuG_DuRatIon
aFtER_SLuG
DRIVE_GaIn_DaMPInG
When the value is “not apply”, they do not
perform.
When the value is “apply”, they perform.
If gas measurement is ordered, this parameter
is not available. the value is “not apply”.
103
2103
DRIVE_GaIn
-
-
this parameter indicates a drive gain value.
When the value of SLuG_aLaRM_SELECt
is “not apply” this function does not perform.
104
2104
SLuG_CRItERIa
11 V
o/S
this parameter indicates a level of drive
gain when an alarm should happen. When
the value of SLuG_aLaRM_SELECt is
“not apply”, users can not change this
value. Range 0 to 11 V.
*) Depends on detector size. For RCCF31 not combined with detector, data for RCCS36 are stored.