A2.2 setting and change of basic parameters, A2.3 setting the ai func- tion blocks – Yokogawa RotaMASS 3-Series User Manual
Page 128

APPENdIX 2. APPLICATION, SETTING ANd CHANGE OF BASIC PArAMETErS
a-28
IM 01R04B05-00E-E 3rd edition July 30, 2010 -00
all Rights Reserved. Copyright © 2005, Rota Yokogawa
A2.2 Setting and Change
of Basic Parameters
this section describes the procedure taken to set
and change the parameters for each block. ob-
taining access to each parameter differs depend-
ing on the configuration system used. For details,
refer to the instruction manual for each configura-
tion system.
access the parameter to be set or changed.
Make setting or change in accordance with
each parameter.
Set the target of block mode (MoDE_BLK)
back to auto
(*note 2)
.
access the block mode (MoDE_BLK) of each
block.
Fa0201.EPS
Set the target
(*note 1)
of block mode
(MoDE_BLK) to auto, Man or o/S
(*note 2)
according to the Write Mode of the parameter
to be set or changed.
note 1: Block mode consists of the following four modes that
are controlled by the universal parameter that displays
the running condition of each block.
target: Sets the operating condition of the block.
actual: Indicates the current operating condition.
Permit: Indicates the operating condition that the block
is allowed to take.
normal: Indicates the operating condition that the block
will usually take.
note 2: the followings are the operating conditions which the
individual blocks will take.
TA0202.EPS
Automatic
(Auto)
Manual (Man)
AI Function
Blocks
Transducer
Block
Resource
Block
Out of Service
(O/S)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
note: Refer to appendix 1, “List of parameters for each block
of RotaMaSS” for details of the Write Mode for each block.
A2.3 Setting the AI Func-
tion Blocks
Each RotaMaSS contains six aI function blocks
(aI1 to aI6) having independent parameters.Set
up the parameters of each aI block you use, indi-
vidually as necessary.
The AI1 block performs the mass flow rate
output calculation.
(1)-1. Setting the calibration range
FA0202.EPS
Access the XD_SCALE parameter.
Set the required unit in Unit Index of
XD_SCALE.
Set the upper range limit in EU at 100% of
XD_SCALE.
Set the lower range limit in EU at 0% of
XD_SCALE.
Example:
to measure 0 to 100t/h,
Set t/h (1328)*
1
in units Index of XD_SCaLE,
Set 100 in Eu at 100% of XD_SCaLE, and
Set 0 in Eu at 0% of XD_SCaLE.
(1)-2. Setting the output scale
FA0203.EPS
Access the OUT_SCALE parameter.
Set the required unit in Unit Index of OUT_SCALE.
Set the output value corresponding to the upper
range limit in EU at 100% of OUT_SCALE.
Set the output value corresponding to the lower
range limit in EU at 0% of OUT_SCALE.
Example:
to set the output range to 0.00 to 100000.00kg/h,
Set kg/h( 1324)*
1
in units Index of out_SCaLE,
Set 100000 in Eu at 100% of out_SCaLE,
Set 0 in Eu at 0% of out_SCaLE.
The AI2 block performs the volume flow out-
put calculation.
(2)-1. Setting the calibration range
FA0202.EPS
Access the XD_SCALE parameter.
Set the required unit in Unit Index of
XD_SCALE.
Set the upper range limit in EU at 100% of
XD_SCALE.
Set the lower range limit in EU at 0% of
XD_SCALE.