6 block setting, 2 function block execution control, 1 link objects – Yokogawa RotaMASS 3-Series User Manual
Page 29: Set the parameter for function block vfd

5. CONFIGUrATION
5-5
IM 01R04B05-00E-E 3rd edition July 30 2010 -00
all Rights Reserved. Copyright © 2005, Rota Yokogawa
T0504-2.EPS
13
FasDllSubscriber
SynchronizationDlcep
Not used for the Rotamass.
14
FmsVfdId
Sets VFD for the Rotamass
to be used.
0x1: System/network
management VFD
0x1234: Function block
VFD
15
FmsMaxOutstanding
ServiceCalling
Set 0 to Server. It is not
used for other applications.
16
FmsMaxOutstanding
ServiceCalled
Set 1 to Server. It is not
used for other applications.
17
FmsFeatures
Supported
Indicates the type of services
in the application layer. In the
Rotamass, it is automatically
set according to specific
applications.
S
ub
-
index
P
arameter
D
escription
12
FasDllSubscriberTime
WindowSize
Not used for the Rotamass.
these 33 VCRs are factory-set as shown in table
5.5.
Table 5.5 VCr List
T0505.EPS
I
ndex
(SM)
VCR
N
umber
F
actory
S
etting
293
For system management (Fixed)
1
294
Server (LocalAddr = 0xF3)
2
295
Server (LocalAddr = 0xF4)
3
296
Server (LocalAddr = 0xF7)
4
297
Trend Source (LocalAddr = 0x07,
Remote Address=0x111)
5
298
Publisher (LocalAddr = 0x20)
6
299
Alert Source (LocalAddr = 0x07,
Remote Address=0x110)
7
300
Server (LocalAddr = 0xF9)
8
9 to 33
Not set
301 to 325
5.5.2 Function Block Execution Control
according to the instructions given in Section 5.3,
set the execution cycle of the function blocks and
schedule of execution.
5.6 Block Setting
Set the parameter for function block VFD.
5.6.1 Link Objects
a link object combines the data voluntarily sent by
the function block with VCR. Each RotaMaSS
has 40 link objects. a single link object speci-
fies one combination. Each link object has the
parameters listed in table 5.6. Parameters must
be changed together for each VCR because the
modifications made to each parameter may cause
inconsistent operation.
Table 5.6 Link Object Parameters
T0506.EPS
S
ub
-
index
P
arameters
D
escription
1
LocalIndex
Sets the index of function
block parameters to be
combined; set “0” for Trend
and Alert.
2
VcrNumber
Sets the index of VCR to
be combined. If set to “0”,
this link object is not used.
3
RemoteIndex
Not used in the Rotamass.
Set to “0”.
5
StaleCountLimit
4
ServiceOperation
Set one of the following.
Set only one each for link
object for Alert or Trend.
0: Undefined
2: Publisher
3: Subscriber
6: Alert
7: Trend
Set the maximum number
of consecutive stale input
values which may be
received before the input
status is set to BAD. To
avoid the unnecessary
mode transition caused
when the data is not
correctly received by
subscriber, set this
parameter to “2” or more.
Link objects are not factory-set. Set link objects as
shown in table 5.7.
Table 5.7 Settings of Link Objects (example)
t0507.EPS
Index
Link object #
Settings(example)
30000
aI. out VCR#6
1
30001
2
30002
3
30003 to 30039
no used
4 to 40
trend VCR#5
alert VCR#7