beautypg.com

16 cls scaling values – Watlow CLS User Manual

Page 46

background image

38 CLS User’s Guide

Installation

16 CLS Scaling Values

For linear mVdc, Vdc, and mAdc ranges, use 0.1% tolerance resistors.
Higher tolerances may cause significant errors. Correct any errors due
to resistor tolerance with the CLS’ built-in linear scaling. You can also
install other components (like capacitors) for signal conditioning; please
consult Watlow Anafaze for more information.

The next table shows scaling resistor values.

The next table shows the location of RC and RD on the analog input
board. (The analog input board is the upper board of the two-board set.)

A wire trace on the printed circuit board jumpers the RC position. When
you place a resistor in the RC position, cut the wire trace that connects
the two resistor terminals.

Input Range

RC

RD

All T/C, 0-60 mV DC

Jumper

0-10 mA DC
0-20 mA DC

Jumper
Jumper

6.0 ohms
3.0 ohms

0-100 mV
0-500 mV

499 ohms
5.49 Kohms

750 ohms
750 ohms

0-1 VDC
0-5 VDC
0-10 VDC
0-12 VDC

6.91 Kohms
39.2 Kohms
49.9 Kohms
84.5 Kohms

422.0 ohms
475.0 ohms
301.0 ohms
422.0 ohms

Loop #

RC

RD

Loop #

RC

RD

1

R58

R42

9

R57

R41

2

R56

R40

10

R55

R39

3

R54

R38

11

R53

R37

4

R52

R36

12

R51

R35

5

R50

R34

13

R49

R33

6

R48

R32

14

R47

R31

7

R46

R30

15

R45

R29

8

R44

R28

16

R43

R27

Analog

IN +

RD

CLS Measurement

Circuitry

Analog
Input
Terminals

RC

Common

IN +