Example 2, Situation, Setup – Watlow CLS User Manual
Page 124
![background image](/manuals/359043/124/background.png)
116 CLS User’s Guide
Linear Scaling
Example 2
Situation
A flow sensor connected to the CLS measures the flow in a pipe. The
sensor generates a 0-5V signal. The sensor's output depends on its
installation. Independent calibration measurements of the flow in the
pipe indicate that the sensor generates 0.5 volts at three gallons per
minute (GPM) and 4.75 volts at 65 GPM. The calibration instruments
are precise to ñ1 gallon per minute.
Setup
The sensor is connected to a loop input set up with a resistor voltage
divider network to produce 60 millivolts at 5 volts. (See the Inputs
section of the Installation chapter for information on scaling networks.)
The calibrating instrument is precise to ±1 gallon per minute, so the
appropriate display format is -999 to +3000.
This table shows the input readings.
The scaling values are therefore:
PV
Displayed
Sensor
Input
Reading (%FS)
65 GPM
4.75
(4.75V / 5.00V) x 100%=95%
3 GPM
0.5
(0.5V / 5.00V) x 100%=10%
Parameter
Low Value
High Value
Process Value (PV)
3 GPM
65 GPM
Input Reading (RDG)
10.0
95.0