Appendix B: Enhanced Process Control

157

Now press Back several times until the normal loop display appears.

The setpoint of loop 2 will now be equal to one half of the process
variable of loop 2. To complete the ratio setup, configure both loops 1
and 2 for inputs, outputs, and alarms. Please consult the Setup section of
the manual for information on PID loop setup.

Enter the minimum Ratio loop SP. For
this example, we will use 0 gallons per
minute as a minimum

Press Enter.

Enter the maximum Ratio loop SP. For
this example, we will use 7.0 gallons per
minute as a maximum

Press Enter.

Enter the control ratio, which is the mul-
tiple applied to the master Process Vari-
able (the H

2

O flow rate is multiplied by

0.5 to obtain the KOH flow rate set-
point).

Press Enter.

Enter the setpoint differential (or offset).
For this example we have no offset
requirement and will use 0

Press Enter.

Display

User Input

LOOP PROCESS UNITS

ALARM SETPOINT STATUS OUT%

02 RATIO CONTROL

MIN SP? 0.0

LOOP PROCESS UNITS

ALARM SETPOINT STATUS OUT%

02 RATIO CONTROL

MAX SP? 7.0

LOOP PROCESS UNITS

ALARM SETPOINT STATUS OUT%

02 RATIO CONTROL

CTRL: RATIO? 0.5

LOOP PROCESS UNITS

ALARM SETPOINT STATUS OUT%

02 RATIO CONTROL

SP DIFF.? 0