Setting Up and Tuning PID Loops
After you have installed your control system, tune each control loop and
then set the loop to automatic control. (When you tune a loop, you
choose PID parameters that will best control the process.) If you don't
mind minor process fluctuations, you can tune the loop in automatic
control mode. This section gives PID values for a variety of heating and
cooling applications.
If you don't know the PID values that are best for your process, try the
CLS Autotune feature. The autotune feature is accessible from the
controller's Man/Auto key. (For more information about Autotune, see
Using the CLS.)
NOTE
Tuning is a slow process. After you have adjusted a loop,
allow about 20 minutes for the change to take effect.
Proportional Band (PB) Settings
The table below shows PB settings for various temperatures in
degrees F.
As a general rule, set the PB to 10% of the setpoint below 1000
º
and 5%
of the setpoint above 1000
º
. This setting is useful as a starting value.
Temperature
Setpoint
PB
Temperature
Setpoint
PB
Temperature
Setpoint
PB
-100 to 99
20
1100 to 1199
75
2200 to 2299
135
100 to 199
20
1200 to 1299
80
2300 to 2399
140
200 to 299
30
1300 to 1399
85
2400 to 2499
145
300 to 399
35
1400 to 1499
90
2500 to 2599
150
400 to 499
40
1500 to 1599
95
2600 to 2699
155
500 to 599
45
1600 to 1699
100
2700 to 2799
160
600 to 699
50
1700 to 1799
105
2800 to 2899
165
700 to 799
55
1800 to 1899
110
2900 to 2999
170
800 to 899
60
1900 to 1999
120
3000 to 3099
175
900 to 999
65
2000 to 2099
125
3100 to 3199
180
1000 to 1099
70
2100 to 2199
130
3200 to 3299
185