beautypg.com

Copying the setup from another profile, Editing the tolerance alarm time – Watlow CLS User Manual

Page 130

background image

122 CLS User’s Guide

Appendix A: Ramp Soak

Copying the Setup from Another Profile

Use this menu to setup similar profiles quickly, by copying a profile to
another one.

Selectable Values: A to Q.

Editing the tolerance Alarm Time

Use this menu to set a tolerance time that applies to the entire profile.

When the segment goes out of tolerance,

The segment goes into tolerance hold

The segment timer holds

The loop’s single loop display shows TOHO (Tolerance Hold)

When the segment has been out of tolerance for more than the tolerance
alarm time,

The controller goes into tolerance alarm

The tolerance timer resets

You must acknowledge the tolerance alarm by pressing the ALARM
ACK key before you can do any other editing.

Selectable Values: 0:00 to 99:59 (minutes or hours, depending on the
time base setting).

LOOP PROCESS UNITS

ALARM SETPOINT STATUS OUT%

COPY SETUP
FROM PROFILE? A

LOOP PROCESS UNITS

ALARM SETPOINT STATUS OUT%

A OUT-OF-TOLRNCE
ALARM TIME? 1:00