Introduction

CLS User’s Guide 9

Digital Inputs

Number: 8

Configuration: 8 selectable for output override, remote job selection.

Input Voltage Protection: Diodes to supply and common. Source must
limit to 10 mA for override conditions.

Voltage Levels: <1.3V=Low; >3.7V=High (TTL).

Maximum Switch Resistance to Pull Input Low: 1 Kohms.

Minimum Switch Off Resistance: 11 Kohms.

User-Selectable Digital Outputs

Number: 34

Operation: Open collector output; On state sinks to logic common.
Current

20 mA for 35 loads. Single load

40 mA. I total

700 mA.

Function: Selectable as PID control or alarm/control.

Number of PID Control Outputs per PID Loop: 2 (max)

PID Control Output Types: Time Proportioning, Distributed Zero
Crossing, SDAC, or On/Off

all independently selectable for each

output. Heat and cool control outputs can be individually disabled for
use as alarm outputs.

Time Proportioning Cycle Time: 1-255 seconds, programmable for
each output.

PID Control Action: Reverse (heat) or direct (cool), independently
selectable for each output.

Off State Leakage Current: <.01 mA to DC common.

System Digital Outputs

System Digital Outputs: 1 Global Alarm, 1 CPU watchdog.

Operation: Open collector output; On state sinks to logic common.
Current

20 mA for 35 loads. Single load

40 mA. I total

700 mA.