6 zone output signal – IAI America PCON-CY User Manual
Page 79

69
5. Operation Using I/O Signals
5.3.6
Zone Output Signal
This signal remains ON while the actuator is inside the zone set in the position table.
The zone output signal can be set only at a single point, but a different zone can be set for the move command corresponding
to each target position (rear end, front end, or intermediate point).
Use the zone output signal in the following situations.
[1] Set an interlock signal to prevent contact with peripheral equipment.
[2] Set a trigger signal for peripheral equipment to reduce the tact time.
[3] Detect missed work during push-motion operation.
[4] Determine the end point when positioning to a series of aligned works via constant pitch feed.
(Note) In constant pitch feed, the “Position” field indicates a relative distance. However, the zone is still set as an
absolute coordinate from the home.
[Setting example]
Rear end
Front end
Intermediate point
Position
[mm]
Zone +
[mm]
Zone –
[mm]
Comment
Zone output signal
Home
Rear end
Move command to the rear end
Move command to the front end
Move command to the intermediate point
+ side limit
Front end
Intermediate
point
Zone output signal
Zone output signal