40

5. Operation Using I/O Signals

5. Operation Using I/O Signals

This chapter explains the wiring/connection and operation timings you should know to perform positioning operation using a
PLC and I/O signals.
For PIO pattern, two types are available. The movement complete signals have different meanings in each type, so select an
appropriate type according to your specific application.
* The factory setting is to use the LS mode.

5.1 Interface

Circuit

The standard interface circuit conforms to the NPN specification, but the PNP specification type is also available as an option.
To simplify wiring, a common power line is used for both the NPN specification and PNP specification. Accordingly you need
not reverse the power connections when using the PNP specification.

5.1.1

External Input Specifications

Item Specification

Number of input points

4 points

Input voltage

24 VDC

± 10%

Input current

5 mA per circuit

Operating voltage

ON voltage:

Min. 18 V (3.5 mA)

OFF voltage: Max. 6 V (1 mA)

Leak current

Max. 1 mA per point

Insulation method

Photocoupler

Internal circuit configuration

[NPN specification]

[PNP specification]

Controller

Controller

+24-V external

power supply

+24-V external

power supply

Each

input

Each

input

Internal circuit

Internal circuit