7. T

roubleshooting

Code

Error Cause/action

0CE

Low control power-supply
voltage

This alarm indicates that the voltage of the 24-V input power supply is low (24 V - 20%:
19.2 V or below).
Cause:

[1] The voltage of the 24-V input power supply is low.
[2] Faulty part in the controller

Action:

Check the input power-supply voltage.
If the voltage is normal, contact IAI.

0D8

Deviation overflow

The position deviation counter has overflowed.
Cause:

[1] The speed dropped while the actuator was moving due to external force,

etc.

[2] Unstable excitation detection operation after the power was turned on

Action:

[1] Check the load condition, such as whether the work is contacting any

peripheral equipment or the brake is released, and remove the cause of
the identified problem.

[2] Overload condition is suspected, so check the load.

0D9

Software limit overshoot
error

Cause: [1] The actuator installed in vertical configuration overshot and exceeded a

soft limit when the target position was near the soft limit and the load was
large or the deceleration setting was high.

[2] The actuator was moved to a position outside the soft limits with the

servo turned OFF, and then the servo was turned ON.

Action: [1] Set a deceleration curve that will not cause the actuator to overshoot

when stopping.

[2] Return the actuator to within the soft limits first, and then turn ON the

servo.