IAI America PCON-CY User Manual
Page 113
103
7. T
roubleshooting
Code
Error Cause/action
0F4
Inconsistent PCB
This controller uses a different motor drive circuit depending on the motor capacity,
and therefore the installed printed circuit board (PCB) is also different with each
controller.
During the initialization after starting, the controller checks if the motor type set by the
manufacturer’s parameter matches the actual PCB installed.
This alarm indicates that the two do not match.
Cause:
The parameter may not be entered correctly or the PCB may not be
assembled correctly.
Action:
If you have encountered this error, contact IAI.
0F5
Nonvolatile memory
verification error after write
When data has been written to the nonvolatile memory, the written data is read and
compared (verified) against the written data for confirmation.
This alarm indicates that the read data does not match the written data.
Cause: [1]
Faulty
nonvolatile
memory
[2] The memory has been rewritten more than 100,000 times. (The nominal
life of the nonvolatile memory is 100,000 rewrite operations.)
Action:
If the problem still persists after the power has been reconnected, contact
IAI.
0F6
Nonvolatile memory
timeout after write
This alarm indicates that no response was received within the specified time after
writing data to the nonvolatile memory.
Cause: [1]
Faulty
nonvolatile
memory
[2] The memory has been rewritten more than 100,000 times. (The nominal
life of the nonvolatile memory is 100,000 rewrite operations.)
Action:
If the problem still persists after the power has been reconnected, contact
IAI.
0F8
Damaged nonvolatile
memory
Abnormal data was detected in the nonvolatile memory check after starting.
Cause: [1]
Faulty
nonvolatile
memory
[2] The memory has been rewritten more than 100,000 times. (The nominal
life of the nonvolatile memory is 100,000 rewrite operations.)
Action:
If the problem still persists after the power has been reconnected, contact
IAI.
0FA
CPU error
The CPU is not operating correctly.
Cause: [1]
Faulty
CPU
[2] Malfunction due to noise
Action:
If the problem still persists after the power has been reconnected, contact
IAI.