53MT6000 INSTRUCTION MANUAL

74 Database Editor

Note that none of these parameters affect the configuration port on the 53MC5000 Controller front port.

MicroLink Mode (Mbits/s):

MicroLink communications Baud rate (Mb/s) [B448 MicroLink
only]. Available selections are:

2
0.5
0.25

Gateway Mode:

Selects the type of Gateway operation. DataLink Responder
mode permits the connection of MicroLink instruments to a
DataLink master. DataLink Interrogator mode permits the
connection of DataLink instruments to a MicroLink network. [L260].
Available selections are:

Datalink Responder
Datalink Interrogator

Gateway Enable:

Available selections are Enabled or Disabled.

Datalink Delay:

This parameter specifies the time in 10ms increments that the
DataLink Interrogator gateway waits for a response. For DataLink
networks with SCADA adapters, this value should be set to
accommodate RTS-CTS delays of transmitted and received
messages, as well as the data rate of the SCADA adapter RS232
port. [B289]

Microlink Retry Disable:

Set to Disable to deactivate MicroLink gateway message retries.
This value should normally be set Enable when the gateway
functions in DataLink Responder mode. It should also be set to
Enable if the gateway functions in DataLink Interrogator mode and
only one or two MicroLink Supervisor cards are generating all of
the messages [L262]. Available selections are:

Enable
Disable

Auto Connect Disable:

Set to Disable (1) to deactivate automatic updating of the DataLink
Node List (B608-B629) when the gateway is set up in DataLink
Interrogator mode. This parameter has no affect when the
53MC5000 is configured in DataLink Responder mode [L263].
Available selections are:

Enable
Disable

OK:

Saves changes, closes window and returns to main menu.

Save:

Saves changes without closing window.

Cancel:

Cancels changes and returns to main menu.

ENTRY

EXPLANATION