Micromod Micro-DCI: 53MT6000 Micro-Tools User Manual
Page 100
53MT6000 INSTRUCTION MANUAL
84 Database Editor
Communications Mode -
Digital:
This parameter selects whether discrete (digital) values are being
transferred as part of the communications. A minimum of one word
(16 L- values) is transferred even if only one L- value is used. [DDIA
= B664, DDIB = B640]
0 = No data exchange
1 = Reads only, from the OPTO 22 to the controller
2 = Reads and writes
3 = Writes only, from the controller to the OPTO 22
Active Boards 0-15
(Digital):
This parameter is used to specify the number of active boards with
addresses starting with address 0. The boards must have
sequential addresses. [DDIA = B665, DDIB = B641]
Active Boards 16 - 31
(Digital):
This parameter is used to specify the number of active boards with
addresses starting with address 16. The boards must have
sequential addresses. [DDIA = B666, DDIB = B642]
Out Mods Even 0-15
(Digital):
This parameter is used to specify the number of output modules per
board. Each board must be configured identically even if positions
are unused. This applies to even numbered addressed boards from
0 to 15. [DDIA = B667, DDIB = B643]
Out Mods Odd 0-15
(Digital):
This parameter is used to specify the number of output modules per
board. Each board must be configured identically even if positions
are unused. This applies to odd numbered addressed boards from
0 to 15. [DDIA = B668, DDIB = B644]
Out Mods Even 16-31
(Digital):
This parameter is used to specify the number of output modules per
board. Each board must be configured identically even if positions
are unused. This applies to even numbered addressed boards from
16 to 31. [DDIA = B669, DDIB = B645]
Out Mods Odd 16-31
(Digital):
This parameter is used to specify the number of output modules per
board. Each board must be configured identically even if positions
are unused. This applies to odd numbered addressed boards from
0 to 15. [DDIA = B670, DDIB = B646]
Watchdog Time 0-15
(Digital):
This parameter is used to specify the watchdog condition.
Assuming a loss of communications, the OPTO 22 boards will
perform one of the following functions. This applies to all boards
from 0 to 15. [DDIA = B671, DDIB = B647]
0 - Watchdog disabled
1 - After 10 seconds, turn off all outputs
2 - After 1 minute, turn off all outputs
3 - After 10 minutes, turn off all outputs
4 - Watchdog timer disabled
5 - After 10 seconds, turn on output 0, turn off all other outputs
6 - After 1 minute, turn on output 0, turn off all other outputs
7 - After 10 minutes, turn on output 0, turn off all other outputs
ENTRY
EXPLANATION