53MT6000 INSTRUCTION MANUAL

Database Editor 85

Watchdog Time 16-31
(Digital):

This parameter is used to specify the watchdog condition.
Assuming a loss of communications, the OPTO 22 boards will
perform one of the following functions. This applies to all boards
from 16 to 31. [DDIA = B672, DDIB = B648]

0 - Watchdog disabled
1 - After 10 seconds, turn off all outputs
2 - After 1 minute, turn off all outputs
3 - After 10 minutes, turn off all outputs
4 - Watchdog timer disabled
5 - After 10 seconds, turn on output 0, turn off all other outputs
6 - After 1 minute, turn on output 0, turn off all other outputs
7 - After 10 minutes, turn on output 0, turn off all other outputs

Communications Mode
- Analog:

This parameter selects whether analog values are being transferred
as part of the communications. [DDIA = B674, DDIB = B650]

0 = No data exchange
1 = Reads only, from the OPTO 22 to the controller
2 = Reads and writes
3 = Writes only, from the controller to the OPTO 22

Active Boards 32-39
(Analog):

This parameter is used to specify the number of active boards with
addresses starting with address 0. The boards must have
sequential addresses starting at 32. [DDIA = B675, DDIB = B651]

Analog Modules/Board:

This parameter is used to specify the number of analog modules per
board. Each board must be configured identically even if positions
are unused. [DDIA = B676, DDIB = B652]

Analog Outputs/Board:

This parameter is used to specify the number of analog output
modules per board. Analog output modules on each board must be
grouped beginning with module position 0. Each board must be
configured identically even if positions are unused. [DDIA = B677,
DDIB = B653]

Read Analog Command:

This parameter is used to specify the type of analog value to be
read. [DDIA = B678, DDIB = B654]

76 = Read Analog Inputs
85 = Read Input Average Data
108 = Read Temperature Inputs
97 = Read Lowest Values
98 = Clear Lowest Values
99 = Read and Clear Lowest Values
100 = Read Peak Values
101 = Clear Peak Values
102 = Read and Clear Peak Values

ANI Type - Boards 32, 33,
36, 37:

This parameter is used to specify the type of analog modules per
board. Each board must be configured identically even if positions
are unused. [DDIA = B679, DDIB = B655]

ANI Type - Boards 34, 35,
38, 39:

This parameter is used to specify the type of analog modules per
board. Each board must be configured identically even if positions
are unused. [DDIA = B680, DDIB = B656]