beautypg.com

Micromod Micro-DCI: 53MT6000 Micro-Tools User Manual

Page 72

background image

53MT6000 INSTRUCTION MANUAL

56 Database Editor

ENTRY

EXPLANATION

Tagname:

Tagname of the CON module [A00].

Output Track
Status:

Displays the current status value of the Output tracking. A
1 indicates the output value is coming from the Output
Track value. A 0 indicates the output comes from the
control modules automatic or manual output value [L105].

Output Track
Switch:

This parameter is used in conjuction with the Output Track
Enable to select output tracking [L117]:
Do Not Track
Track

Output Track
Enable:

This parameter is used to disable or enable output tracking
[L119]:
Tracking Disabled
Tracking Enabled

Hard Manual
Limit:

This parameter enables or disables the output limit
checking. When enabled, the Output High and Output Low
Limits are applied to the output signal [L122]:
Disabled
Enabled

Output:

This parameter is the output of the Auto/Manual selector.
This output normally represents the final output of the
controller [C102].

Output High
Limit:

High output limit value [C109]

Output Low
Limit:

Low output limit value [C110]

Output Slew
Rate:

Output rate limit [C118]

Control Output:

This displays the calculated output of the PID function
[C123].

Output Track
Value:

This parameter is the output value applied to the Auto/
Manual Selector when the Output Tracking Status is equal
to 1.

OK:

Saves changes, closes window and returns to main menu.

Save:

Saves changes without closing window.

Cancel: