beautypg.com

7 status configurable parameters, Figure 7-16. status parameter configuration window – Micromod Micro-DCI: 53MT6000 Micro-Tools User Manual

Page 78

background image

53MT6000 INSTRUCTION MANUAL

62 Database Editor

7.4.7.7 STATUS Configurable Parameters

The control module STATUS parameters may be configured by clicking on the STATUS button. The win-
dow shown in

Figure 7-16

will be displayed. The database locations where these values are stored for

CON0 are shown in brackets [ ].

Figure 7-16. Status Parameter Configuration Window

ENTRY

EXPLANATION

SP Track Status:

Displays the current status value of the Setpoint tracking. A
value of 1 indicates the setpoint value is coming from the
Setpoint Track Value. A value of 0 indicates the output comes
from the control module’s remote or local setpoint value [L104].

Auto Status:

Displays status of Automatic/Manual selection. A value of 1
indicates the control output is provided by the PID function. A
value of 0 indicates the control output is manually adjusted by
the operator.

Remote Status:

Displays status of Remote/Local Switch selection.

Auto Switch:

Available selections [L112]:
Manual
Auto

SP Track Switch:

This parameter is used in conjunction with the Setpoint Track
Enable to select the Setpoint Track Mode. The control module’s
setpoint is forced to track the Setpoint Track Value when the
Setpoint Track Status is set to 1. Available selections [L116]:
Do Not Track
Track

Control Track
Command:

This database parameter is used in conjunction with the Reset
Feedback. When the control Track Command is 1 the reset
feedback is ignored by the PID calculation. When the Control
Track Command is 0, the reset feedback is used by the PID
calculation to avoid PID windup. [L123]