Micromod Micro-DCI: 53MT6000 Micro-Tools User Manual
Page 102
![background image](/manuals/337714/102/background.png)
53MT6000 INSTRUCTION MANUAL
86 Database Editor
Samples to Average:
This parameter is used to specify the number of 100 ms samples to
be taken for averaging. This value applies to all analog inputs.
[DDIA = B681, DDIB = B657]
Watchdog Time 32-39
(Analog):
This parameter is used to specify the watchdog condition.
Assuming a loss of communications, the OPTO 22 boards will
perform one of the following functions. This applies to all boards
from 32-39. [DDIA = B673, DDIB = B649]
0 - Watchdog disabled
1 - After 10 seconds, write zero scale
2 - After 1 minute, write zero scale
3 - After 10 minutes, write zero scale
4 - Watchdog timer disabled
5 - After 10 seconds, write full scale
6 - After 1 minute, write full scale
7 - After 10 minutes, write full scale
Watchdog Time 16-31
(Analog):
This parameter is used to specify the watchdog condition.
Assuming a loss of communications, the OPTO 22 boards will
perform one of the following functions. This applies to all boards
from 16 to 31. [DDIA = B672, DDIB = B648]
0 - Watchdog disabled
1 - After 10 seconds, turn off all outputs
2 - After 1 minute, turn off all outputs
3 - After 10 minutes, turn off all outputs
4 - Watchdog timer disabled
5 - After 10 seconds, turn on output 0, turn off all other outputs
6 - After 1 minute, turn on output 0, turn off all other outputs
7 - After 10 minutes, turn on output 0, turn off all other outputs
ENTRY
EXPLANATION