4 modbus slave parameter configuration, Figure 7-30. modbus slave configuration window – Micromod Micro-DCI: 53MT6000 Micro-Tools User Manual
Page 107
53MT6000 INSTRUCTION MANUAL
Database Editor 91
7.4.16.4 Modbus Slave Parameter Configuration
Once the preferred PLC device has been selected, a separate configuration window specific to the inter-
face is displayed, as shown in
.
Figure 7-30. Modbus Slave Configuration Window
ENTRY
EXPLANATION
Mode:
This displayed value represents the index number of the PLC type.
[DDIA = B290, DDIB = B456]
Baud Rate:
This designates the data transfer rate. Clicking on the "down arrow"
reveals a list of 11 selections, these are [DDIA = B292, DDIB = B458]:
110
300
600
1200
2400
4800
9600
19200
14400
28800
38400
Set UP:
This designates the data format transfer protocol. Clicking on the
"down arrow" reveals a list of 3 selections, these are [DDIA = B293,
DDIB = B459]:
8, 1, NO
8, 1, EVEN
8, 1, ODD
Self Address:
This is the 53MC5000 source address used in all messages to the
Allen Bradley unit. [DDIA = B670, DDIB = B646]