Micromod Micro-DCI: 53SL6000 Single Loop Controller User Manual
Page 58
Table 6-3. Logic Block Parameters
(ProG Menu
→ LG Module)
Prompt
Description
Dft
LG1.M
LG2.M
LG3.M
LG4.M
Logic Blocks 1 - 4 Mode Select
These mode parameters are used to
select the logical operation to be
performed on the inputs of the logic
blocks. Function selections for each
block are as follows:
oFF: No logical operation
performed.
or: A OR B.
/or: NOT A OR B.
And: A AND B.
/And: NOT A AND B.
Xor: A EXCLUSIVE OR B.
/Xor: NOT A EXCLUSIVE OR B.
or/: A OR NOT B.
And/: A AND NOT B.
oFF
oFF
oFF
oFF
LG1.A
LG1.b
LG2.A
LG2.b
A and B Inputs for Logic Blocks 1
and 2
Specifies the connections for the A
and B inputs of logic blocks 1 and 2.
Input selections are as follows:
[1]: Logical one input.
[0]: Logical zero input.
di1: Discrete input 1 logic value.
/di1: Inverted di1 logic value.
di2: Discrete input 2 logic value.
/di2: Inverted di2 logic value.
di3: Discrete input 3 logic value.
/di3: Inverted di3 logic value.
di4: Discrete input 4 logic value.
/di4: Inverted di4 logic value.
di5: Discrete input 5 logic value.
/di5: Inverted di5 logic value.
di6: Discrete input 6 logic value.
/di6: Inverted di6 logic value.
di7: Discrete input 7 logic value.
/di7: Inverted di7 logic value.
di8: Discrete input 8 logic value.
/di8: Inverted di8 logic value.
do7: Loop-back do7 register value.
/d07: Inverted loop-back do7
register value.
d08: Loop-back do8 register value.
/d08: Inverted loop-back do8
register value.
Fnc: Math function block digital
output.
chr: Characterizer output.
[1]
[1]
[1]
[1]
Table 6-3. Logic Block Parameters
(ProG Menu
→ LG Module)
Prompt
Description
Dft
LG3.A
LG3.b
LG4.A
LG4.b
A and B Inputs for Logic Blocks 3
and 4
Specifies the connections for the A
and B inputs of logic blocks 3 and 4.
Input selections are as follows:
[1]: Logical 1 input.
[0]: Logical 0 input.
PA1: cn.1 AL1 active.
PA2: cn.1 AL2 active.
Vup: Floating control valve up.
Vdn: Floating control valve down.
SWA: Auto switch.
SWr: Remote switch.
Aut: Loop 1 is in auto control.
rMt: Remote.
oVtS: Output track status.
SPtS: Setpoint track status.
PA1.2: cn.2 AL1 active.
PA2.2: cn.2 AL2 active.
Aut.2: Loop 2 is in auto control.
Fnc: Math function block digital
output.
chr: Characterizer output.
LG1: Logic block 1 output.
LG2: Logic block 2 output.
[1]
[1]
[1]
[1]
Table 6-4. Discrete Logic Block Functions
A OR B (or)
A AND NOT B (And/)
A
B
LG1-4
A
B
LG1-4
0
1
1
0
1
0
1
1
1
1
1
0
0
0
0
0
0
0
1
0
1
1
0
1
A AND B (And)
NOT A OR B (/or)
A
B
LG1-4
A
B
LG1-4
0
1
0
0
1
0
1
1
1
1
1
0
0
0
0
0
0
1
1
0
0
1
0
0
A XOR B (Xor)
NOT A AND B (/And)
A
B
LG1-4
A
B
LG1-4
0
1
1
0
1
1
1
1
0
1
1
0
0
0
0
0
0
1
1
0
1
1
0
1
A OR NOT B (or/)
NOT A XOR B (/Xor)
A
B
LG1-4
A
B
LG1-4
0
1
0
0
1
0
1
1
1
1
1
1
0
0
1
0
0
1
1
0
1
1
0
0
Micro-DCI
53SL6000 Controller